Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts
FACP with Keltron
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
123
APPENDIX D 
 
FACP with Keltron
The following figure illustrates the connections between the FACP and Keltron Reveiver/
Transmitter.  
CAUTION!  For reasons of wiring diagram clarity, terminal designations of Keltron modules are 
not shown in actual order.  Follow Keltron manual and module markings for exact terminal 
locations to prevent severe module damage!
IMPORTANT! All connections between the FACP and Keltron modules must be made within 20 
feet and enclosed within conduit or equivalently protected against mechanical injury. 
   Fire Alarm Control Panel
(terminal blocks are not shown in 
their actual positions in order to 
clarify wiring connections)
Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
Note: Cut TBL jumper on 4XTMF module to send 
alarm/trouble signal from the same pair or terminals.
Alarm/Trouble Signal
Sprinkler Supervisory Signal
*Note: For more information, 
refer to Keltron manual.
4XTMF Module