Installation
Operating Power
20
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
2.2 Operating Power
WARNING: Several different sources of power can be connected to this panel.  Disconnect all 
sources of power before servicing.  The panel and associated equipment may be damaged by 
removing and/or inserting cards, modules or interconnecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet.  The primary power source for the 
panel is 120 VAC, 60 Hz, 3.66 amps for the MRP-2001 or 240 VAC, 50 HZ, 2.085 amps for the 
MRP-2001E.  Run a pair of wires (with ground conductor) from the protected premises main 
breaker box to the AC terminal block TB1 on the main power supply.  As per the National 
Electrical Code, use 14 AWG (2.00 mm
2
, 1.6 mm O.D.) or heavier gauge wire with 600V 
insulation.  No other equipment may be connected to this circuit.  In addition, this circuit must be 
provided with overcurrent protection and may not contain any power disconnect devices.  A 
separate Earth Ground connection must be made to ensure proper panel operation and lightning and 
transient protection.  Connect the Earth Ground wire [minimum 14 AWG (2.00 mm
2
)] to the 
grounding stud in the backbox.  Do not use conduit for the Earth Ground connection since this does 
not provide reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery.  Connect the battery cable to J12 on the main circuit 
board using the plug-in connector and cable provided.  The battery charger is current-limited and 
capable of charging sealed lead acid batteries.  The charger shuts off when the system is in alarm.
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and 
can destroy fabrics.  If contact is made with sulfuric acid, immediately flush the skin or eyes with 
water for 15 minutes and seek immediate medical attention.
 
!
Figure 2.4 Operating Power Connections
120 VAC Power
Hot (L1)
Ground
Neutral (L2)
Ground Wire
J12
Batteries
rp2001powr.cdr
+
-