Input Circuits
Installation
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
21
2.3 Input Circuits
The MRP-2001 has six programmable IDCs (Initiating Device Circuits).  Each circuit is compatible 
with System Sensor’s i
3
 smoke detectors which generate a maintenance signal when the detector 
becomes dirty and a separate supervisory ‘freeze’ signal when ambient temperature falls below the 
detector rating of approximately 45
o
F.  The maximum loop resistance limit for each IDC is 100 
ohms.  The maximum number of detectors per zone is 25.  The field wiring for each zone is 
supervised for opens, shorts and ground faults.  All conditions are visually and audibly 
annunciated.
Each circuit is configured for Style B (Class B) operation and will accept i
3
 smoke detectors, any 
normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors. 
Refer to the Device Compatibility Document for a list of compatible devices.
Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A 
Converter module.  Refer to  "CAC-5X Class A Converter Module" on page 26.  
Figure 2.5 IDC Connections
Class B Initiating Device Circuits (supervised and power-limited) 4.7 K
Ω
, ½ watt resistor P/N:71252
manual pull stations
heat detectors
Dummy load all unused 
circuits - 4.7 K
Ω
, ½ watt 
resistor (P/N: 71245)
m
rp-2001idc.cdr
UL listed Power Supervision Relay
(refer to Device Compatibility Document for list of compatible relays)
Resettable 24 VDC 
4-wire smoke 
detector power 
(500 mA maximum)
UL listed compatible 4-wire smoke detector
manual 
release
Input IDC 
Waterflow Circuit 
Normally Open 
Waterflow 
Devices or 
Pressure Switches