3.5.6.3.4 Daylight Savings Time
Pressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed: 
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between 
Enabled Yes and Enabled No.  The control panel will automatically update the time for daylight 
savings time when Enabled Yes is selected.
Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows 
the programmer to select the month that daylight savings time will begin.  In this sub-screen, 
pressing 1 will select March, 2 will select April and 3 will select May.
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow 
the programmer to select the week of the month that daylight savings time will begin.  In the 
first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will 
select the third week, while in the second sub-screen, pressing 1 will select the fourth week and 
2 will select the last week of the selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows 
the programmer to select the month that daylight savings time will end.  In this sub-screen, 
pressing 1 will select September, 2 will select October and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow 
the programmer to select the week of the month that daylight savings time will end.  In the first 
sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will select 
the third week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will 
select the last week of the selected month.
3.5.6.4 Trouble Reminder
The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for 
alarms and troubles, after the panel has been silenced.  Refer to  "System Setup" on page 64, for 
a detailed description of this feature.  Pressing 2 while viewing System Setup Screen #2 will 
cause the display to toggle to Trouble Remind Yes, which enables this feature.  Each press of the 
2 key will cause the display to toggle between Trouble Remind Yes and Trouble Remind No.
Note that if the Trouble Reminder feature is not enabled, a trouble existing on the panel for 
more than 24 hours will cause the FACP to resound the trouble sounder.
3.5.6.5 Charger Disable
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to enable or 
disable the onboard battery charger.  If an external battery charger is being used, the onboard 
battery charger must be disabled.  Each press of the 3 key will toggle between Chargr Disable 
No
 and Chargr Disable Yes.
   TIME AND DATE
1=DAYLIGHT SAVINGS
Time & Date Screen #2
  DAYLIGHT SAVINGS
1=ENABLED        YES
2=START MONTH    MAR
3=START WEEK     WK 2
Daylight Savings Screen #1  
Daylight Savings Screen #2  
  DAYLIGHT SAVINGS
1=END MONTH      NOV
2=END WEEK       WK 1
   SYSTEM SETUP
1=TIME-DATE
2=TROUBLE REMIND
3=CHARGR DISABLE