TO ENTER PROGRAMMING MODE:
Local programming requires the use of an alpha keypad connected to the keypad terminals on the control.
1. POWER UP, then depress [
] and [#]  both at once, within 50 seconds of powering up.
OR
2. Initially, key: Installer Code (default = 4112) plus 8 + 0 + 0.
(if 
98 was used to exit previously, see 
To Exit Programming Mode paragraph below.
Data Field Programming Procedures
Task
Procedure
Go to a Data Field
Press [
] + [Field Number], followed by the required entry.
Entering Data
When the desired field number appears, simply make the required entry. When the last
entry for a field is entered, the keypad beeps three times and automatically displays the
next data field in sequence.
If the number of digits that you need to enter in a data field is less than the maximum
digits available (for example, the phone number fields *41, *42), enter the desired data,
then press [
] and the next data field number to be programmed to end the entry.
Review a Data Field
Press [#] + [Field Number].
Data will be displayed for that field number. No changes will be accepted in this mode.
Deleting an Entry
Press [
] + [Field Number] + [
]. (Applies only to fields 
40–*46, *94, and pager
programming fields)
Interactive Mode Programming (
56, *57,  
58, 
79, 
80, 
81, 
82)
Press [
] + [Interactive Mode No.] (for example, 
56). The alpha display keypad will display the first of a series of prompts
requesting entries.
Interactive Mode
Used to Program
56 Zone Programming
Zone characteristics, report codes, alpha descriptors, and serial numbers for 5800
RF transmitters.
57 Function Key Programming
Unlabeled keypad keys (known as ABCD keys) for special functions
58 Zone Programming
Same options as *56 mode, but with fewer prompts. Intended for those familiar with
(Expert mode)
this type of programming, otherwise *56 mode is recommended.
79 Output Device Mapping
Assign module addresses and map individual relays/powerline carrier devices
80 Output Programming
4229 or 4204 Relay modules, Powerline Carrier devices, or on-board triggers
81 Zone List Programming
Zone Lists for relay/powerline carrier activation, chime zones, pager zones, etc.
82 Alpha Programming
Zone alpha descriptors
INITIALIZE DOWNLOAD and RESET DEFAULTS
96 Initializes download ID and subscriber account number.
97 Sets all data fields to original factory default values.
TO EXIT PROGRAMMING MODE:
98 Exits programming mode and 
prevents  re-entry by:  Installer Code 8 + 0 + 0. To reenter the programming mode,
the system must be powered down, then powered up, then press both [
] and [#] at same time within 50 seconds
of powering up (method 1 described above), UNLESS  Local Lockout (in field *91) is enabled.  If so, re-entry to
programming mode is permitted 
only by Installer Code 8 + 0 + 0 (method 2 described above).
99 Exits programming mode and 
allows  re-entry by: Installer Code + 8 + 0 or method 1 above.
Special Messages
OC = OPEN CIRCUIT (no communication between Keypad and Control).
EE or ENTRY ERROR = ERROR (invalid field number entered;  re-enter valid field number).
After powering up, AC, dI (disabled) or Busy Standby and NOT READY will be displayed after approximately 4 seconds.
This will revert to a “Ready” message in approximately 1 minute, which allows PIRS, etc. to stabilize. You can bypass this
delay by pressing [#] + [0].
If E4 or E8 appears, more zones than the expansion units can handle have been programmed. Correct the programming
and then completely de-power and re-power the control to clear this indication and remove the disable indication.