Enerco ERXL-175L Benutzerhandbuch

Seite von 28
16
Enerco | enerRadiant® XL Series Heater
Operating Instructions and Owner’s Manual
SECTION 4
Venting / Ducting
 
General Requirements
Heater must be vented in accordance with specification ANSI Z223.1 
- latest revisions. Partial information relating to this specification is 
provided in this section with regard to size and configurations for 
venting arrangements (see Figures 12, 13, 14, 15, 16). For complete 
information consult ANSI Z223.1 - latest revision and applicable local 
codes. Use the following guidelines to help insure an adequate, safe 
venting arrangement.
 
a)  Be sure that method selected for venting 
heater complies with all codes as required for 
each particular location.
 
b)  Exhaust end of heater will accept a four (4”) 
inch flue pipe using the flue pipe adapter.
 
c)   Heater may be vented to the outdoors either 
vertically or horizontally.
 
d)  If heater is to be vented horizontally:
 
1)  Vent must exit building not less than seven (7’) 
feet above grade when located adjacent to public 
walkways.
 
2)  Vent must terminate at least three (3’) feet above 
any forced air inlet located within ten feet (10’).
 
  3)Vent must terminate at least four (4’) feet below, 
four (4’) feet horizontally from, or one (1’) foot 
above any door, window, or gravity inlet into any 
building.
 
4)   Vent terminal shall be located at least twelve (12”) 
inches from any opening through which vent gases 
could enter the building.
 
e)  Vent terminal must be beyond any combustible 
overhang.
 
f)  If condensation in the flue is a problem, the 
flue length should be shortened or insulated.
 
g)  For vent specifications all of the following 
conditions must be met.
 
1)  Maximum total vent length allowed in forty-five 
(45’) feet.
 
2)  Maximum outside air supply duct allowed forty-five 
(45’) feet.
 
3)  Maximum total vent length plus outside air supply 
length plus extension package shall not exceed sixty 
-five (65’) feet.
 
4)  Under length conditions 1) through 3) above — a 
total of two (2) elbows are allowed for vent and 
outside air supply together. Subtract fifteen (15’) 
feet per additional elbow from maximum length 
allowed if more than two (2) elbows are used.
Alternative Arrangements / Optional Equipment for Venting
Unvented Operation 
 
a)   Sufficient ventilation must be provided in the 
amount of 4 CFM per 1,000 BTU/hr. firing rate.
 
b)  Refer to ANSI Z223.1 - latest revision, NFPA-54 
and local codes for additional information.
 
c)  Use of optional outside combustion air is not 
recommended with unvented heaters due to 
pressure considerations.
Horizontal Venting 
 
a)  In combustible or noncombustible walls, 
use Tjerblund VH1-4” (Stk. #19022). Follow 
vent manufacturer’s instructions for proper 
installation. (Alternative vent Enerco Stk. 
#19023).
 
b)   Four (4”) inch O.D. flue pipe is required. Thirty 
(30’) feet maximum length is recommended. 
Up to forty-five (45’) feet maximum may 
be used if insulated to prevent excess 
condensation. (See General Requirements on 
page 21 for additional information).
 
c)  All flue joints should be sealed using suitable 
product such as General Electric RTV106 or 
Permatex Form-A-Gasket Red High Temperature 
Silicone Adhesive Sealant.
 
d)  Vent terminal should be installed at a height 
sufficient to prevent blockage by snow.
 
e)  Building materials should be protected from 
degradation by flue gases.
Vertical Venting  a)  Four (4”) inch O.D. flue pipe, maximum 
forty-five (45’) feet in length may be used as 
shown with approved vent cap. (See General 
Requirements on page 21 for additional 
information.)
 
b)  An insulated thimble may be required to pass 
through combustible structures (check local 
codes).
 
c)   All flue joints should be sealed using suitable 
products (see recommendation for horizontal 
venting.)
Draft Hood Venting 
 
a)   Refer to ANSI Z223.1 - latest revision, NFA-54 
for heights and vent sizes recommended 
for proper venting. (Check local codes for 
additional information.)
 
b)  Minimum six (6”) inch O.D. vent is 
recommended.
Common Venting 
 
a)  Horizontal run to vent must never exceed 75% 
of the vertical height of the vent. Refer to ANSI 
Z223.1 - latest revision, NFA-54 for proper vent 
sizes and installation.
 
b)  Open area of common vent must equal the 
sum of the open area of individual vents 
connected to it. (See chart and diagrams - 
page 25.)
 
c)   Use double wall vent as required (check 
codes.)
 
d)  Heaters sharing a common vent must be 
controlled by the same thermostat.
 
e)   All joints must be sealed using suitable 
products (see recommendation for horizontal 
vent - page 24.)
 
f)  Connections to common stack must be 
positioned to avoid direct opposition between