Quadra-Fire 5100I-GD-B Benutzerhandbuch

Seite von 44
5100-I  ACT WOOD INSERT
Page 1
April 21, 2010
438-0380E
   
 D.  Masonry Chimney
  • Must meet minimum standards of NFPA 11.
  • Must  have  at  least  5/8  inch  (16mm)  fireclay  lining  joined 
with refractory cement.   (Installations into a clay flue without 
a  stainless  steel  liner  may  reduce  draw  which  affects
performance,  will  cause  the  glass  to  darken  and  produce 
excessive creosote).
 •
The masonry wall of the chimney, if brick or modular block, 
must be a minimum of  inches (10mm) nominal thickness.
 •
A chimney of rubble stone must be at least 12 inches (305mm)
thick.
 • Cross-sectional  area  should  be  no  more  than  3  times  the
cross-sectional area of the flue collar of the insert.  (8 sq inch 
flue area x  inches = 8 square inches maximum chimney 
area).
  • Should be lined with a 6 inch (15mm) stainless steel flue liner 
to improve performance and reduce creosote build-up.
 
• 
An equivalent liner must be a listed chimney liner system or 
other approved material.
  • No dilution air is allowed to enter the chimney.
 
1.
Secure the fireplace damper in the open position.  If this 
cannot be accomplished, it will be necessary to remove
the damper
    . Seal damper area of chimney around chimney connector 
with a high temperature sealant or seal insert against the
face of the fireplace.
 
3. Both  methods  must  be  removable  and  replaceable  for
cleaning and re-installation.
 • When possible, install an airtight clean-out door to the rear of
the smoke shelf.
Minimum 1/2” (25mm) Air Space,
Maximum 4” (102mm) Air Space
Airtight Clean-
Out Door
Minimum 5/8” (16mm) 
Fireclay Flue Liner
Non-Water Soluble 
Refractory Mortar
4“ (102mm) Masonry 
or Modular Block Wall 
(Nominal)
12” (305mm) if Rubble 
Stone Wall (Nominal)
Footing (depth and size of footing 
accordance with local building code)
Figure 14.1
A.  Venting Systems
Chimney Connector:
It is also known as flue pipe or stove pipe.  It must be 
6  inches  (152mm)  minimum  diameter  stainless  steel
connector pipe.
Chimney
:
The  chimney  can  be  new  or  existing,  masonry  or 
prefabricated  and  must  meet  the  following  minimum
requirements as specified below.
WARNING! Risk of Fire!
Follow  venting  manufacturer’s  clearances  and
instructions when installing venting system.
B.  Inspections
Existing chimneys should be inspected and cleaned by a
qualified professional prior to installation.  The chimney 
must not have cracks, loose mortar or other signs of dete-
rioration and blockage.  Hearth & Home recommends a 
NFI or CSIA certified professional or a technician, under 
the direction of a certified professional, conduct a Level II 
inspection per NFPA 11.
Fire Risk
Inspection of Chimney:
Chimney must be in good condition.
•  Meets minimum standard of NFPA 11
•  Factory-built chimney must be 6 inch 
(15mm) UL10 HT.
WARNING
NOTICE:  Check  with  your  local  building  authorities 
and/or consult the National Fire Protection Association 
(NFPA 11).  
C.  Larger Chimneys
It  is  recommended  that  chimneys  with  larger  diameters
than  6  inches  (15mm)  be  relined.    An  oversized  flue 
can  affect  draft  and  impair  performance  and  will  allow
increased build-up of creosote.
4
Chimney Requirements