5100-I  ACT WOOD INSERT
438-0380E
April 21, 2010
UL 1777 Insulated Stainless Steel 
Liner or Other Approved Lining System 
Follow Manufacturer’s Instructions 
on Insulation and Support 
For Zero or Other Non-Code Clearances, 
Follow Approved Liner Manufacturer’s Specific 
Insulation Requirements:  Different Clearances 
May Require Different Specifications 
Masonry Chimney Must 
Have Structural Integrity 
UL 1777 Insulated Stainless Steel 
Liner or Other Approved Lining System 
Minimum 8 in. (203mm) Masonry 
Thickness in Front of Smoke Chamber
Damper Plate Removed or 
Fastened in Open Position 
Seal with Non-Combustible Material 
Minimum Clearance in Accordance 
with Insert Listing 
Floor Protection in 
Accordance with Insert 
Listing 
Follow Manufacturer’s 
Instructions for Maximum 
Liner Extension Above 
Chimney 
Maximum 30
 
Degrees 
Offset in Chimney 
Combustible Floor 
Masonry Chimney (Cont’d)
Figure 15.1
NOTE:
  In Canada, this fireplace insert must be installed 
with a continuous chimney liner of a 6 inch (152mm) diam-
eter extending from the fireplace insert to the the top of the 
chimney.  The chimney liner must conform to the Class  
requirements of CAN/ULC-S65, Standard for Lining Sys-
tems for Existing Masonry or Factory-Built Chimneys and 
Vents,  or  CAN/ULC-S60,  Standard  for  Lining  Systems 
for New Masonry Chimneys.
The Quadra-Fire 5100-I Insert conforms with the UL 18 
and ULC S68 (Canada) in all respects, and is approved to 
UL & ULC safety standards for installation and use within a 
fireplace with a masonry chimney in accordance with NFPA 
11 and CAN/CSA-B65-01.
NOTE:
  
Installation into fireplaces without a permit will 
void the listing.