Empire Products BF-30-2 Benutzerhandbuch

Seite von 20
16012-1-0504
Page 5
SPECIFICATIONS
Specifications
Model
BF-10
BF-20
BF-30
Input BTU/HR (KW/H) (LP)
10,000 (2.9)
20,000 (5.8)
30,000 (8.8)
Input BTU/HR (KW/H) (NAT)
10,000 (2.9)
18,000 (5.3)
30,000 (8.8)
Height
22" (559mm)
22" (559mm)
22" (559mm)
Width
18" (457mm)
18" (457mm)
24 1/8" (536mm)
Depth
6 1/2" (165mm)
6 1/2" (165mm)
61/2" (165mm)
Gas Inlet
3/8" (10mm)
3/8" (10mm)
3/8" (10mm)
Accessories
Blower
SRB-18T
SRB-18T
SRB-30T
Floor Stand
SRS-18*
SRS-18
SRS-30
*SRS-18 floor stand can not be used in a bedroom installation.
BF-10 must be wall mounted in a bedroom installation.
The bedroom must be an unconfined space. ANSI Z223.1/NFPA 54 defines an unconfined space as "a space whose volume is not less
than 50 cubic feet per 1,000 Btu per hour (4.8m
3
 per kw) of the aggregate input rating of all appliances installed in that space."
INTRODUCTION
Instructions to Installer
1. Installer must leave instruction manual with owner after
installation.
2. Installer must have owner fill out and mail warranty card
supplied with unvented room heater.
3. Installer should show owner how to start and operate unvented
room heater.
Always consult your local Building Department  regarding regu-
lations, codes or ordinances which apply to the installation of an
unvented room heater.
This appliance may be installed in an aftermarket* permanently
located, manufactured (mobile) home, where not prohibited by
state or local codes.
*Aftermarket: Completion of sale, not for purpose of resale, from
the manufacturer.
This appliance is only for use with the type of gas indicated on the
rating plate. This appliance is not convertible for use with other
gases.
General Information
This BF-10, BF-20 and BF-30 are design certified in accordance
with American National Standards Institute Z21.11.2 by the
Canadian Standards Association as an Unvented Room Heater
and should be installed according to these instructions.
Any alteration of the original design, installed other than as
shown in these instructions or use with a type of gas not shown
on the rating plate is the responsibility of the person and
company making the change.
WARNING: This appliance is equipped for (natural gas or
propane) gas. Field conversion is not permitted.
Important
All correspondence should refer to complete Model Number,
Serial Number and type of gas.
Qualified Installing Agency
Installation and replacement of gas piping, gas utilization equip-
ment  or accessories and repair and servicing of equipment shall
be performed only by a  qualified agency.  The term "qualified
agency" means any individual, firm, corporation, or company that
either in person or through a representative is engaged in and is
responsible for (a) the installation, testing, or replacement of gas
piping or (b) the connection, installation, testing, repair, or servic-
ing of equipment; that is experienced in such work; that is familiar
with all precautions required, and that has complied with all the
requirements of the authority having jurisdiction.
The installation must conform with local codes or, in the absence
of local codes, with the National Fuel Gas Code, ANSI Z223.1/
NFPA54
.*
*Available from the American National Standards Institute, Inc.,  11 West 42nd
St., New York, N.Y. 10036.
High Altitudes
For altitudes/elevations above 2,000 feet (610m), ratings should
be reduced at the rate of 4 percent for each 1,000 (305m) feet
above sea level.  Contact the manufacturer or your gas com-
pany before changing spud/orifice size.
Well Head Gas Installations
Some natural gas utilities use "well head" gas. This may affect the
Btu output of the unit. Contact the gas company for the heating
value. Contact the manufacturer or your gas company before
changing spud/orifice size.