Installation
Only For Qualified Installers
Making The Connection
The gas inlet is located on the bottom right side 
of the fireplace. The inlet fitting is 1/2” male flare fitting 
designed for 1/2” stainless flex pipe. This fitting can be 
removed to provide 3/8” female pipe thread.
A  separate  gas  shut-off  valve  and  a  1/8”  N.P.T. 
plugged  tapping  should  be  installed  immediately  up-
stream of the connection to the appliance.
The ShadowLight XL Direct Vent Gas Heater must 
be disconnected from the gas supply piping during any 
pressure testing of that system at pressures in excess 
of 1/2 psig (3.5 kPa).
The  ShadowLight  XL  gas  control  valve  must  be 
in the OFF position during any pressure testing of the 
gas supply system at pressures equal to or less than 
1/2 psig (3.5 kPa).
WARNING: To avoid pipe compounds from enter-
ing into the gas train, apply compounds only to male 
pipe  threads  and  do  not  apply  compound  to  the  first 
two threads.
CAUTION: TEST ALL JOINTS FOR LEAKS BE-
FORE OPERATING.
 
Gas Pressure Requirements:
Correct  gas  pressure  and  the  use  of  a  properly 
sized gas supply line are essential for the safe and ef-
ficient performance of this appliance. Make sure that 
the plumber or gas supplier checks the gas supply line 
and gas pressure at installation.
 NOTE: Improper gas pressure can affect heater 
performance, flame color, or cause pilot outage.
Natural Gas:
 
Maximum inlet pressure 7.0” w.c. (1.74 kPa)   
Minimum inlet pressure 5.0” w.c. (1.25 kPa)  
Gas manifold pressure 3.5” w.c. (0.87 kPa)
LP Gas:
 
Maximum inlet pressure 13” w.c. (3.24 kPa)   
Minimum inlet pressure 11” w.c. (2.74 kPa)  
Gas manifold pressure 10” w.c. (2.49 kPa)
DO NOT USE THIS HEATER IF ANY PART HAS 
BEEN  UNDER  WATER,  EXPOSED  TO  MOISTURE, 
OR SHOWS SIGNS OF CORROSION. IMMEDIATELY 
CALL A QUALlFlED SERVICE TECHNICIAN TO IN-
SPECT THE HEATER AND REPLACE ANY PART OF 
THE CONTROL SYSTEM AND ANY GAS CONTROL 
WHICH HAS BEEN UNDER WATER.
Gas Line
CONNECTING THE SHADOWLIGHT XL 
FIREPLACE INSERT TO A GAS SUPPLY
Test Class 
Note:  Stove  is  built  for  propane. A  conversion 
must be done to accomodate natural gas.
Do  not  connect  the  venting  to  the  flue  of  a 
chimney  that  serves  a  separate  solid-fuel 
burning appliance.