Energy Tech Laboratories DSH Benutzerhandbuch

Seite von 24
JOHNSON CONTROLS
4
FORM 145.32-IOM1 (908)
GENERAL INFORMATION 
Our  units  are  designed  to  meet  the  ever-changing 
(unique) installation requirements of today’s market. The 
horizontal configuration is unitized for single package 
or split installation. Low profile design allows the unit to 
be installed on the floor or suspended from the ceiling. 
All unit components are securely mounted inside the 
heavy gauge “Galvalume” sheet metal cabinet. All units 
are lined with a 1/2 in. thick – 21lb density acoustical 
insulation to ensure the quietest operation. All models 
are shipped with medium-efficiency 2-in. thick throw-
away filters. Multi-position filter rack is external to the 
cabinet. 
Unit can be turned on its side for short periods of time, 
which  allows  passage  through  standard  door  sizes. 
Removal of the cross supports on the top and sides will 
convert packaged unit into a split system, allowing the 
condensing  section to be installed remotely from the 
evaporator section. 
Horizontal units 2, 3, 4 & 5 ton models have a single 
refrigerant circuit configuration. All models are equipped 
with an adjustable thermal expansion valve (with exter-
nal equalizer), one valve per circuit. Each refrigerant 
circuit is also equipped with a liquid line filter drier, sight 
glass/moisture indicator and easy access service gauge 
ports. All 2-5 ton models are shipped as factory-charged 
unitized packages. The 2-5 ton units include refrigerant 
line shut-off valves to allow the units to be field split. 
Installation time is minimized with all models. When plan-
ning an installation consider power supply, thermostat, 
condensate drain line, duct run, servicing allowances, 
and load points. A remote thermostat control device is 
field supplied and installed to control the units operation. 
Each refrigerant circuit is equipped with auto-reset high 
pressure and low pressure switches. Each circuit is con-
stantly monitored by ComfortAlert module. By monitoring 
and analyzing data from the Copeland Scroll compressor 
and the thermostat demand, the module can accurately 
detect the cause of electrical and system related failures 
and protect the compressor.  A flashing LED indicator 
communicates the ALERT code and guides the service 
technician more quickly and accurately to the root cause 
of a problem. Control circuit is 24-volt operation with 
oversized transformer. Optional anti-short circuit timers 
can be field/factory installed. 
Service access doors are equipped with handles and 
are located on all sides of the unit to allow easy servic-
ing of all components. Service access doors are factory 
shipped  with  knock-outs  allowing  gauge  lines  to  be 
installed and pressure readings to be taken while the 
machine is operating. In addition there is a removable 
panel on the access door so visual observation of the 
sight glass is possible without removing the access door. 
All units are equipped with centrifugal blowers combined 
with variable pitch adjustable pulleys. Forward curved 
double width and inlet centrifugal blowers are used for 
condenser & evaporator air movement. All models em-
ploy a draw-through air flow system. All blower wheels 
are  galvanized  steel,  with  solid  steel  shafts  and  are 
equipped with permanently lubricated ball bearings. V-
belt driven blowers are used in all models; RPM can be 
adjusted through the variable pitch motor sheave. 
ONLY QUALIFIED PERSONNEL SHOULD 
PERFORM  INSTALLATION AND  SER-
VICE OF THIS EQUIPMENT. 
High efficiency scroll compressors are used in all mod-
els, mounted on durable rubber isolator pads reducing 
vibration and noise while operating. Large evaporator 
and condenser coil face areas reduce noise levels, air 
pressure drops and minimize potential for condensate 
blow off. All models are equipped with copper tube and 
rippled aluminum plate fin coils. 
Units will operate reliably at an outdoor ambient down 
to 60 deg F.