9-1-3. LED Display on Indoor P.C. Board
1. D002 (Red)
• Goes on at the same time when power was turned on (Main microcomputer operates and goes on.)
• Flashes with 1-second interval (every 500ms): When EEPROM is not provided or writing was an error.
• Flashes with 10-seconds interval (every 5S): When the mode is DISP
2. D203 (Red)
• Goes on when power is supplied to remote controller (Lights on the hardware)
9-1-4. Function Selection Setup
<Procedure> Perform setting while the air conditioner stops.
1
Push 
TEST
 + 
SET
 + 
CL
 buttons simultaneously for 4 seconds or more.
The first displayed unit No. is the master indoor unit address in the group control.
In this time, fan and louver of the selected indoor unit operate.
ò
2
Every pushing 
UNIT  LOUVER
 button (button at left side), the indoor unit No. in the group control is
displayed one after the other. In this time, fan and louver of the selected indoor unit only operate.
ò
3
Using the set temperature 
TEMP.
 buttons, specify the CODE No. (DN).
ò
4
Using the timer time 
TIME
 buttons, select the set data.
ò
5
Push 
SET
 button. (OK if indication lights)
• To change the selected indoor unit, proceed to Procedure 
2
 .
• To change item to be set up, proceed to Procedure 
3
 .
ò
6
Pushing 
TEST
 button returns the status to the normal stop status.
1    2    3    4    5    6
  END   
<Operation procedure>
3
6
1
4   
5   
2   
SET
TIMER SET
TEST
FILTER
LL
RESET
TEMP.
CL
FAN
SWING/FIX
VENT
MODE
ON / OFF
UNIT  LOUVER
T