– 57 –
Function selection item No. (DN) list
DN
01
03
06
10
11
12
13
14
1E
28
2A
2b
31
32
40
60
C2
D0
Item
Filter sign lighting time
Central control address
Heating suction temp. shift
Type
Indoor unit capacity
Line address
Indoor unit address
Group address
In automatic cooling/heating, temp.
width of cool → heat, heat →
cool mode selection control point
Automatic reset of power failure
Selection of option / error input
(CN70)
Selection of thermostat output
(T10 
ƒ
 )
Fan (Single operation)
Sensor selection
Humidifier control
(+Drain pump control)
(This function is not provided.)
Timer setting
(Wired remote controller)
Current demand X% to outdoor unit
Existence of remote controller save
function
Contents
0000:None
0001: 150H
0002:2500H
0003: 5000H
0004:10000H
0005: Clogging sensor used
0001:No.1 unit
to
0064: No.64 unit
0099:Undecided
0000:No shift
0001: +1°C
0002:+2°C
to
0010: +10°C
(Up to +6 is recommended.)
0000:(1-way air discharge cassette)
0001:(4-way air discharge cassette) to 0038
0000:Undecided
0001 to 0034
0001:No.1 unit
to
0030: No.30 unit
0001:No.1 unit
to
0064: No.64 unit
0000:Individual
0001: Master unit in group
0002:Follower unit in group
0000:0 deg
to
0020: 20 deg
(Cool/heat are reversed with ± (Data value) /
2 against the set temperature)
0000:None
0001: Provided
0000:Filter input
0001:Alarm input (Air cleaner, etc.)
0002:Humidifier input
0000:Indoor thermostat ON
0001:ON receiving output of outdoor compressor
0000:Impossible
0001: Possible
0000: Body TA sensor
0001: Remote controller sensor
0000:No control
0001:Humidifier + Vaporizing type (Pump ON)
0002:Humidifier + Supersonic type
(Pump ON when specified time elapsed)
0003:Humidifier + Natural drain type (Pump OFF)
0000:Operable
0001:Operation prohibited
0050:50%
to
0100: 100%
0000:Invalid (Impossible)
0001: Valid (Possible)
At shipment from factory
According to type
0099:Undecided
0002:+2°C
(Floor type 0000: 0°C)
According to model type
According to capacity type
0099:Undecided
0099:Undecided
0099:Undecided
0003:3 deg (Ts±1.5)
0000:None
0002:Humidifier
0000:Thermostat ON
0000:Impossible
0000:Body sensor
0003:Humidifier ON
Pump OFF
0000:Operable
0075:75%
0001:Valid (Possible)
∗ Restriction ratio setting for save operation (DN code No. [C2]) can be set/changed from the normal DN setup
(Detail DN setup).