American Power Conversion DX Benutzerhandbuch

Seite von 96
51
NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting
View Event Log
The event log saves status information and a message each time a change in the System is detected. 
Alarms and events are recorded in the log. However, status events (informational) are only displayed on 
the active alarms screen. 
View log
Path: Main > View Log 
New Events. 
The New Events option is a log of events that have occurred since the last time the log 
was checked. 
Entire Log. 
The event log keeps a record of all alarms and events. Each event log entry consists of four 
screens of information. The initial screen consists of the following text:
•  The name of the alarm
•  Its index number in the log and the Module to which it applies
•  The time and date the event occurred
•  The name and description of the event
Use the arrow keys to scroll through the list of events. 
To view more details about the event, press the 
E
NTER
 key. This will allow access to three more screens 
(use the arrow keys to switch screens).
•  Temperature and humidity
– Supply temperature and humidity
– Return temperature and humidity
•  Pressures
– Discharge pressure
– Suction pressure
•  Module status
– Condenser fluid valve position
– Output code (for use during service calls)
Clear Log. 
Erase all of the events in the log. When this option is selected, a confirmation screen 
displays and the service password must be entered to erase the log