Operation: Set Up Module Control
NetworkAIR IR Operation, Maintenance, and Troubleshooting
19
Reset compressors
Paths: Main > Setup > Module > Main Module > Module Control > Reset Compressors
Main > Setup > Module > Expansion Module > Module Control > Reset 
Compressors
The Reset Compressors option resets the compressors after an alarm. The compressors shut down 
during a Suction Pressure Low alarm. Use this function to restart the compressors manually when 
the alarm condition is resolved.
Low Suction Pressure alarms indicate a problem with the refrigeration 
system. Check the event log for other alarms before resetting the 
compressors.