NetworkAIR IR Operation, Maintenance, and Troubleshooting
Control the Environment
The System controls the room environment by engaging one of four modes: Cool, Dehumidify, 
Reheat, or Humidify. These modes may work differently depending on the options and equipment 
installed in your Modules.
How the modes work
Cool. 
When the cool mode uses a Chilled Water coil, the output is determined by the difference 
between the setpoint and the measured air temperature (control temperature) of each of the Modules 
in the System (if more than one Module is present). The control temperature can be the average return 
sensor value, the average remote sensor value, or the maximum remote sensor value, depending on 
the System settings (Path: Main > Setup > System > System Setup > System Config > Sensor 
Setup
)
The Proportional plus Integral plus Derivative (PID) control loop calculates the output as demand 
increases and opens the valve controlling the flow of coolant into the coil. The PID adjusts the output 
as required to maintain the temperature at the setpoint. 
Reheat (Electric SCR and Modulating Hot Water). 
The SCR (silicon-controlled rectifier) 
electric reheat function is controlled by the reheat PID controller. The PID controller adjusts the 
output as required to maintain the temperature at the setpoint.
Reheat (Hot Gas, Steam, Hot Water On/Off). 
The output of the hot gas, steam, and hot water 
on/off reheat options is determined by the difference between the setpoint and control temperature of 
the Module. When the control temperature at the Module reaches the setpoint minus the deadband, 
the reheat mode activates until the control temperature rises to the setpoint.
The environmental controls are set when your System is installed. Changing settings 
described in this section after the system has been commissioned may result in 
improper operation.
See “Sensor setup” on page 9 to choose the source of the temperature value which 
the Module uses to calculate demand.
See “PID controls” on page 23 for a description of the PID controls and 
instructions on tuning the fluid coil PID loop.
See “PID controls” on page 23 for a description of the PID controls and 
instructions on tuning the reheat PID loop.
See “Deadbands” on page 22 for acceptable reheat deadband values.