NetworkAIR IR Operation, Maintenance, and Troubleshooting
35
View Status Readings
The display interface has several options for viewing the status of the System, its Modules, and the 
environment being controlled. The status readings for Modules are available under the Main Module 
and Expansion Module # options, and status readings for the System are available under the System 
Status
 option or on the scrolling status screens.
Scrolling status screens
When the display interface is idle, it scrolls through nine screens of status information. Press the up 
or down arrow key to interrupt the automatic scrolling and view a specific status screen. 
Module status
Paths: Main > Status > Main Module
Main > Status > Expansion Module 1
The Module status screens contain information for each Module in a System. 
Temp & Humidity. 
View temperature and humidity readings at the supply, return, and remote 
sensors for each Module. This screen has the same format as the Temp & Humidity scrolling status 
screen, but the values displayed are only for the selected Module.
Pressures. 
View the differential pressures at the coil and the filter for this Module.
Run hours. 
View the total time each of the eight components have been running. 
• Clear Total: Reset the run hours for the displayed component to zero.
• Reset Maint Alarms: Clear the Maintenance alarm for the displayed component. The alarm 
will occur when the run hours reach the next maintenance interval.
Note
Only the Main Module of a System has a display interface. The temperature and 
humidity readings displayed on the scrolling status screens are an average of the 
readings from each of the Modules.
If the System is off, the readings are the values from the sensors of the Main Module. 
To scroll through and clear the total hours, see “Maint intervals” on page 27.