(13) Revision
 
2 = Second version
(14) Heat 
Exchanger
 
E = Glass-lined steel with copper tubes
 
F = Glass-lined steel with cupronickel tubes
(15)  Control Option Code
 
X = Standard, meets CSD-1 boiler standard
 
A = Control Pack A: CSD-1, CA, FM, IL, IRI, 
  
Alarm 
Bell
 
B = Control Pack B: CSD-1, CA, FM, IL, LDS, MN
 
F = Non CSD-1
(16) Pump 
Options
 
N = Pump mounted, normal pump (standard)
 
H = Pump mounted, hard water pump (BRHHV) 
1.3 Warranty
Bradford White’s Brute Magnum appliances 
are covered by a limited warranty. The owner should 
fill out the warranty registration card and return it to 
Bradford White.
All warranty claims must be made to an 
authorized Bradford White representative or directly 
to the factory. Claims must include the serial number 
and model (this information can be found on the rating 
plate), installation date, and name of the installer. 
Shipping costs are not included in the warranty 
coverage.
Some accessory items are shipped in separate 
packages. Verify receipt of all packages listed on 
the packing slip. Inspect everything for damage 
immediately upon delivery, and advise the carrier of 
any shortages or damage. Any such claims should be 
filed with the carrier. The carrier, not the shipper, is 
responsible for shortages and damage to the shipment 
whether visible or concealed.
1.4 Dimensions
The overall dimensions are 34.5" (88cm) 
wide, 65.75" (167cm) tall, 55" (140cm) deep. Other 
dimensions can be found in Figure 1.
1.5 Locating the Appliance
The Brute Magnum is for indoor installations 
only.
The appliance should be located to provide 
clearances on all sides for maintenance and inspection. 
It should not be located in an area where leakage of 
any connections will result in damage to the area 
adjacent to the appliance or to lower floors of the 
structure.
When such a location is not available, it is 
recommended that a suitable drain pan, adequately 
drained, be installed under the appliance. 
The appliance is design certified by CSA-
International for installation on combustible flooring; 
in basements; in closets, utility rooms or alcoves
Brute Magnum Boilers or Water Heaters must 
never be installed on carpeting. 
The location for the 
appliance should be chosen with regard to the vent 
pipe lengths and external plumbing. The unit shall be 
installed such that the gas ignition system components 
are protected from water (dripping, spraying, rain, etc.) 
during operation and service (circulator replacement, 
control replacement, etc.). When vented vertically, the 
Brute Magnum must be located as close as practical 
to a chimney or gas vent. If the vent terminal and/
or combustion air terminal terminate through a wall, 
and there is potential for snow accumulation in the 
local area, both terminals should be installed at an 
appropriate level above grade.
The dimensions and requirements that are shown 
in Table 1 should be met when choosing the locations 
for the appliance:
Appliance 
Clearance From 
Suggested Service
Surface Combustible 
Material 
Clearance
 inches 
 
inches 
Piping Side 
 
18 
Opposite Side 
 
Top 1 
 
24 
Back 1 
 
36 
Front 1 
 
36 
Vent 
per UL1738 venting
 system 
supplier’s
 instructions
Table 1. Clearances.
1.6  Locating Pump-Mounted Water Heater 
with Respect to Storage Tank(s)
For best results the Brute Magnum water heater 
should be located within 15 feet (4.6m) of the storage 
tank(s). The pump is sized for 30 feet (9.1m) of piping.
Water heater pumps are sized for water hardness; 
7.6 to 17 grains per gallon for normal water, greater 
than 17 grains per gallon for hard water, and 1 to 
7.5 grains per gallon for soft water. If the appliance 
must be installed with longer piping runs, then larger 
diameter pipe or tubing may be able to be used, in 
some instances. Consult the factory for assistance.
1.7  Locating Pump-Mounted Boiler with 
Respect to Return/Supply Header
Brute Magnum units must be piped in primary-
secondary fashion because of the internal pump and 
mixing system.
For the best results the Brute Magnum Boiler 
should be located within 15 feet (4.6m) of the supply 
and return headers. The pump is sized for 30 feet 
(9.1m) of piping, in most cases, enough for primary-
secondary piping systems.
If the appliance must be installed with longer piping 
runs, then larger diameter tubing may be able to be used, 
in some instances. Consult the factory for assistance.