Bradford-White Corp BRHHV Benutzerhandbuch

Seite von 56
Brute Magnum
Page 7
Figure 1. Dimensional Drawing.
Size Intake 
Exhaust 
Intake 
Exhaust 
 
Size 
Size 
Maximum Run 
Maximum Run 
1200 
6" (15 cm) dia. 
6" (15 cm) dia. 
50 linear feet with 5 elbows 
50 linear feet with 5 elbows 
1600 
8" (20 cm) dia. 
6" (15 cm) dia. 
50 linear feet with 5 elbows 
50 linear feet with 5 elbows 
2000 
8" (20 cm) dia. 
7" (18 cm) dia. 
50 linear feet with 5 elbows 
50 linear feet with 5 elbows 
2400 
8" (20 cm) dia. 
10" (25 cm) dia. 
50 linear feet with 5 elbows 
50 linear feet with 5 elbows 
Table 2. Vent / Air Pipe Sizes.
1.8  Locating Appliance for Correct Vent 
Distance From Outside Wall or  
Roof Termination
The forced draft combustion air blower in the 
appliance has sufficient power to vent properly when 
the guidelines in Table 2 are followed.
NOTE: When located on the same wall, the Brute 
Magnum combustion air intake terminal must be 
installed a minimum of 12" (30cm) below the exhaust 
vent terminal and separated by a minimum of 
36 inches (91cm) horizontally.
Size
“V”
Vent Outlet
Connection
“A”
Air Inlet
Connection
“W”
Water
Inlet/ Outlet
Connection
“G” Gas Connects.
Control Packages
“B”
Std & A
Nat/ LP
B & E
Nat
B & E
LP
inches
inches
NPT
NPT
NPT
NPT
inches
1200
6
6
2-1/2”
1’
1-1/2’
1-1/2”
34-1/4”
1600
6
8
2-1/2”
1-1/2’
2”
2’
34-1/4”
2000
7
8
3”
1-1/2’
2”
2”
34-1/4”
2400
10
8
3”
1-1/2”
2”
2”
32”