CLEARANCES  TO  COMBUSTIBLES
Floor  Protection
Floor protection under the F 3 CB woodstove, must
be one of the following:
1.  Any non combustible material with an insulative
R value of 1.1.
2.    Any  UL,  ULC  or  WH  hearth  board  or
prefrabricated non-combustible material.
The  bottom  heatshield  (standard  equipment)  is
required in all installations.
Individual  sections  of  floor  protection  must  be
mortared  together  to  prevent  sparks  from  falling
through to combustible materials.  Any carpeting must
be removed from under the floor protection.
In the U.S.and Canada
The F 3 CB must be installed on a non-combustible
surface extending a minimum of 18” (460mm) in front
of the stove and 8” (200mm) on the remaining sides
of the stove (measured from side and back panels).
This will result in a minimum floor protection of
41 D X 39 W   See figure 12.
In a rear vent installation the floor protection must
also extend under the stove pipe a minimum of 2”
(50mm) beyond either side of the pipe.
10
Using  Shields  to  Reduce  Clearances
Pipe shields:  When using listed pipe shields to reduce
the connector clearance to combustibles, it must start
1” above the lowest exposed point of the connect
pipe and extend vertically a minimum of 25” above
the top surface of the stove.
Double wall pipe:  Listed double wall pipe is an
acceptable alternative to connector pipe heatshields.
Wall-Mounted Protection:  When reducing clearances
through the use of wall mounted protection:
In  the  U.S.  refer  to  NFPA  211,  Standard  for
Chimneys,  Fireplaces,  Vents  and  Solid  Fuel
Burning  Appliances,  for  acceptable  materials,
proper sizing and construction guidelines.
In  Canada,  refer  to  CAN/CSA-B365, Installation
Code  for  Solid-Fuel  Burning  Appliances  and
Equipment,  also  for  acceptable  materials,  proper
sizing and construction guidelines.
Stove mounted Rear Heatshield is standard equipment
on all F 3 CB woodstoves.
  
NO   OTHER   STOVE
MOUNTED HEAT  SHIELD   MAY   BE   USED.
18”
460mm
200mm
200mm
200mm
FIGURE 12
 41”
DEEP
  39”
WIDE
front
Clearances to walls and ceilings
The following clearances have been tested to UL and
ULC  standards  and  are  the  minimum  clearances
specifically established for the Jøtul F 3 CB.
The following charts and diagrams give the required
clearances you must maintain when installing the F 3
CB near combustible surfaces.
 A combustible surface is anything that can burn (i.e.
sheet rock, wall paper, wood, fabrics etc.).  These
surfaces are not limited to those that are visible and
also include materials that are behind non-combustible
materials.
If you are not sure of the combustible nature of a
material, consult your local fire officials.
Remember: “Fire Resistant” materials are considered
combustible; they are difficult to ignite, but will burn.
Also  “Fire-rated”  sheet  rock  is  also  considered
combustible.
Contact your local building officials about restrictions
and installation requirements in your area.