 F39 Room Sealed Freestanding Gas Stove
7
LOUVER 
INSTALLATION
1)  Attach the top & bottom louvres to the 
side stove panel using 2 screws per 
side.
INSTALLATION
FLUEING  
INTRODUCTION
The DV Stove Horizontal Flue Kit and the 
Simpson Dura-Flue Room Sealed System 
Model DV-GS fl ueing systems, in combination 
with the Regency
®
 Room Sealed Freestanding 
Gas Stove,  F39-NG, and F39-LPG, have been 
tested and listed as direct fl ue heater systems 
by AGA.
These units use the "balanced  fl ue"  technology 
Co-Axial system. The inner liner fl ues products 
of combustion to the outside while the outer pipe 
draws outside combustion air into the combus-
tion chamber thereby eliminating the need to 
use heated room air for combustion and losing 
warm room air up the chimney.
Note: These fl ue  pipes  must  not  be  con-
nected to any other appliance.
The gas appliance and fl ue system must be 
fl ueed directly to the outside of the building, 
and never be attached to a chimney serving a 
separate solid fuel or gas burning appliance. 
Each direct fl ue gas appliance must use it's own 
separate fl ue system. Common fl ue systems 
are prohibited.
 IMPORTANT
Read all instructions carefully before starting the 
installation. Failure to follow these instructions 
may create a fi re or other safety hazard, and will 
void the warranty. Be sure to check the fl uing 
and clearance to combustible requirements. 
Consult your local building codes before begin-
ning installation.
The location of the termination cap must con-
form to the requirements in the Exterior Flue 
Terminal Locations diagram, refer to "Exterior 
Flue Termination Location" section.
INSTALLATION 
PRECAUTIONS
These fl uing systems are engineered products 
that have been designed and tested for use 
with the F39-NG, and F39-LPG. The warranty 
will be voided and serious fi re, health or other 
safety hazards may result from any of the fol-
lowing actions:
1)  Installation of any damaged Room Sealed 
component
2)  Unauthorized modifi cation of the Room 
Sealed System
3)  Installation of any component part not manu-
factured or approved by Simpson Dura-Flue 
or Fireplace Products International Ltd.
For fl ue termination requirements, refer to "Ex-
terior Flue Termination Location" section.
COMBUSTION AND 
VENTILATION AIR
The combustion air from this appliance is drawn 
from outside the building through the outer fl ue. 
Extra provision for combustion air inside the 
room is not required.
4)  Installation other than as instructed by 
Simpson Dura-Flue and Fireplace Products 
International Ltd.
Warning:  Always maintain required 
clearances (air spaces) to nearby 
combustibles to prevent a fire 
hazard. Do not fi ll air spaces with 
insulation. 
Be sure to check the fl ue termination clearance 
requirements from decks, windows, soffi ts, 
gas regulators, air supply inlets and public 
walkways as specifi ed in the Exterior Flue 
Terminal Locations on page 8 and in your local 
building codes.
The gas appliance and fl ue system must be 
fl ueed directly to the outside of the building, 
and never be attached to a chimney serving 
a separate solid fuel or gas-burning appli-
ance.
 Each direct fl ue gas appliance must use 
it's own separate fl ue system. Common fl ue 
systems are prohibited.
SAFETY PRECAUTIONS 
FOR THE INSTALLER
1)  Wear gloves and safety glasses for 
protection.
2) 
Exercise extreme caution when using 
ladders or on roof tops.
3) 
Be aware of electrical wiring locations 
in walls and ceilings.