The IntelliKnight 5820XL Fire Alarm Control/Communicator is an addressable fire control 
system that meets the requirements of UL 864. 
1.1
Overview of Basic System
The IntelliKnight 5820XL base system is packaged as an assembled stack of 3 circuit boards 
mounted to an aluminum housing.
1.1.1
Hardware Features
The IntelliKnight 5820XL panel has one signaling line circuit (SLC). Up to three 
additional SLC loops can be added using the 5815XL SLC expander. The SLC(s) support 
the SK series addressable detectors and modules or Hochiki protocol detectors and 
modules.
Each SLC supports up to 99 detectors and 99 modules for a total of 396 detectors and 396 
modules per 5820XL panel when using SK series devices. Alternatively, each SLC 
supports up to 127 Hochiki devices for a total of 508 devices per 5820XL panel. 
6.0A of output power is available through 6 sets of terminals for notification and auxiliary 
applications. Each circuit is power limited per UL 864 and can source up to 3.0A (total 
output power for all 6 circuits must not exceed 6.0A).
Built-in dual phone line, digital alarm communicator/transmitter (DACT).
Reports events to central station by point or by zone.
UL Listed for pre-action and deluge releasing systems.
Dedicated Form C trouble relay and two general purpose Form C programmable relays.
Basic system operation can be performed using a key or a user code.
Can be used with up to 8 Model 5860 Remote Annunciators (sold separately).
Supports the 5865-3, 5865-4, and 5880 in any combination for a total of eight devices on 
one control panel. See sections 4.8 and 4.9 for additional information on these models.
Printing of detector status, event history, and real time event log available through the 
Model 5824 Serial/Parallel Printer Interface Module (sold separately).
Supports conventional 2-wire & 4-wire detectors using the 6 Flexput™ circuits.
Add 6 Flexput™ circuits with each 5895XL Intelligent Power Module (up to 8 5895XLs 
per system). See note below.
Add 4 notification/auxiliary power circuits with each 5496 Intelligent Power Module. See 
note below.
Note: The system can support a maximum of eight Intelligent Power modules, either the 5895XL or 5496, in any 
combination.