Honeywell 5820XL Benutzerhandbuch

Seite von 228
IntelliKnight 5820XL Installation Manual
1-2
151209
1.1.2
Software Features 
125 software zones, 250 output groups.
Advanced smoke detector features:
Automatic drift compensation
Maintenance alert region
Point status eliminates calibrated smoke test requirements for NFPA 72
“JumpStart” feature for easy programming
Non-volatile event history stores 1000 events
A choice of output patterns available for notification outputs, including ANSI 3.41 
temporal signal
Built-in synchronization appliance support for AMSECO, Faraday, Gentex
®
, System 
Sensor
®
, and Wheelock
®
.
1.2
About this Manual
This manual is intended to be a complete reference for all installation and operation tasks for 
the 5820XL. Please let us know if the manual does not meet your needs in any way. We value 
your feedback!
1.2.1
Terms Used in this Manual
The following terminology is used with the IntelliKnight 5820XL system:
Table 1-1 Manual Terminology
Term
Description
SLC
Signaling line circuit
Module
The term module is used for all hardware devices except for SLC 
addressable devices and notification appliances. This includes the 5820XL 
panel itself and the built-in 5897 power supply. It also refers to any 
(optional) 5815XL SLC expansion modules.
Input Point
An addressable sensing device, such as a smoke or heat detector or a contact 
monitor device. 
Input Zone
A protected area made up of input points.
Output Point
(or Output Circuit)
A notification point or circuit for notification appliances. Relay circuits and 
auxiliary power circuits are also considered output points.
Group (or “Output Group”)
A group of output points. Operating characteristics are common to all 
output points in the group.
Output (or “Cadence”) Pattern
The pattern that the output will use, for example, Constant, March Code, 
ANSI 3.41. Applies to zones and special system events. See Section 7.7.3.2 
for additional information.
Mapping
Mapping is the process of specifying which outputs are activated when 