Testing and Troubleshooting
151209
10-3
3) When necessary, activation of Notification Appliances can be prevented by the DISABLE 
function
Testing:
1) Activate a input via an alarm initiating device and check that the correct outputs activate 
(Notification Appliances sound/flash, relays activate, alarm LED lights). Reset system. 
Repeat for each alarm initiating device.
       2)   Momentarily open the following circuits one at a time and check for a trouble signal:
Notification Appliance (bell) Circuits.
Initiating devices
        3) If new batteries were installed, wait 48 hours before completing this step. Remove AC 
power, activate initiating device and check that:
The ALARM indicator lights.
All active Notification Appliances sound.
Measure battery voltage while the Notification Appliances are sounding. Replace any battery 
with terminal voltage less than 85% of rating. Reapply AC power and RESET system.
10.2.2 Event History
The event history can be useful for tracking or recalling a trouble condition.