Honeywell 5820XL Benutzerhandbuch

Seite von 228
Testing and Troubleshooting
151209
10-5
10.3.2 SLC Multi Locator
This feature is the same as SLC Device Locator, except you can locate up to 8 devices on a 
single search.
Follow these instructions to locate multiple SLC devices:
1. Select 
 (Point Functions) from the Main Menu.
2. Select 
 (SLC Dev Locator).
A message similar to the one shown in Figure 10-1 will display.
Figure 10-2  Shut Down Warning
3. Press the 
 or 
 arrow to toggle NO to YES then press 
.
If NO is chosen you will exit back to the Point Function menu.
If Yes is chosen the system will cease normal operation leaving the premise unprotected.
4. Select the SLC loop.
5. Enter up to 8 SLC addresses for the devices you wish to locate.
The LEDs on the selected devices will start flashing.
6. Press the 
 to exit SLC multi-locator function.
Note: Once you exit the system will resume normal operation.
2