INSTALLATION
Use only new, black iron or steel pipe. Internally- tinned copper tubing may be used 
in certain areas. Check your local codes. Use pipe of 
1
/
2
" or greater diameter to allow 
proper gas volume to heater. If pipe is too small, undue loss of pressure will occur.
CAUTION
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe 
could result in clogged heater valves.
IMPORTANT: Hold pressure regulator with wrench when connecting it to gas piping and/or fittings. 
Use pipe joint sealant that is resistant 
to liquid petroleum (LP) gas. 
CAUTION
Installation must include an equipment shutoff valve, union, 
and plugged 1/8” NPT tap. Locate NPT tap within reach for 
test gauge hook up. NPT tap must be upstream from heater 
(see Figure 14).
 
IMPORTANT: Install an equipment shutoff valve in an 
accessible location. The equipment shutoff valve is for 
turning on or shutting off the gas to the appliance. 
Figure 14 - Gas Connection
Pipe Coupling
To Gas Log 
Set or to Gas 
Valve
Shutoff
Valve
Gas Supply Inlet 
Pipe
Locations that the Pressure Tapping 
Point May be Installed 
CONNECTING TO GAS SUPPLY 
This  appliance  requires  a  3/8”  NPT 
(National Pipe Thread) inlet connection 
to the pressure regulator.
W
ARNING
A  qualified  service  person  must 
connect heater to gas supply. Follow 
all local codes.
W
ARNING
Never connect heater to private (non-
utility) gas wells. This gas is commonly 
known as wellhead gas.
W
ARNING
The installer must supply an external regulator. The external 
regulator will reduce incoming gas pressure. You must reduce 
incoming gas pressure to between 11 and 14 inches of water 
column. If you do not reduce incoming gas pressure, heater 
regulator damage could occur. Install external regulator with 
the vent pointing down as shown in Figure 13. Pointing the 
vent down protects it from freezing rain or sleet.
Figure 13 - External Regulator with Vent 
Pointing Down
Propane/LP 
Supply Tank 
External 
Regulator 
Vent 
Pointing 
Down