Honeywell R7426A Benutzerhandbuch

Seite von 20
R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK 
EN1B-0203GE51 R0507C 
 
 
config. par. 
R7426 
no. 
name 
description 
default 
setting 
I / II 
A  B  C
actual 
value 
C.12 T2ext 
Enable / Disables the T1 sensor input to be used for both T1 and T2 inputs. 
0 x 
x
 
  
T2 installed 
T1 signal used for T2 
 
 
 
 
 
C.13 LimTyp 
Limitation type determines whether the limit function is low or high. 
0 / 1 
x x x
 
  
Low limit 
High limit 
 
 
 
 
 
C.14 Senstyp 
Sensor type determines automatic detection or manual selection of NTC 
sensors. 
0 x 
x
 
  
Auto detection 
NTC sensor type 
 
 
 
 
 
C.15 Y1CTRF 
Controls the action of Y1 or activates the occupancy input for summer/winter 
changeover. 
0 / 1 
x  x  x
 
 
 
R7426A R7426B,C 
 
 
 
 
 
  
cooling 
heating 
summer/winter changeover 
1 
mixed air damper 
energy recovery 
 
 
 
 
 
C.16 AddHour
2)
  Adjusts the month for winter/summer time change. 
3 x 
x
 
 
 
Min. 
Max. 
(disables winter/summer time change) 
12 
(
March)   
 
 
 
C.17 SubHour
2)
  Adjusts the month for summer/winter time change. 
10 x 
x
 
 
 
Min. 
Max. 
0 (disables summer/winter time change) 
12 
(
Oct.) 
 
 
 
 
C.18  PSTG_H
2) 3)
  Determines the prestart gradient to reach the comfort setpoint for heating. 
0 K/min  x  x  x
 
 
 
Min. 
Max. 
0 (disabled) 
2 
 
 
 
 
 
C.19  PSTG_C
2) 3)
  Determines the prestart gradient to reach the comfort setpoint for cooling. 
0 K/min  x  x  x
 
 
 
Min. 
Max. 
0 (disabled) 
2 
 
 
 
 
 
C.20 tvd
2)
 
Determines the damper prestart time before scheduled comfort mode 
15 min 
  x  x
 
 
 
Min. 
Max. 
(normal control) 
90 
 
 
 
 
 
C.21 Adapt
2)
 
Optimum Start Self Adaption speed 
50% x 
x
 
 
 
Min. 
Max. 
0 
100 
 
 
 
 
 
C.22 Adr
1)
 
Sets the serial communication address, used for service or maintenance. 
254 x 
x
 
 
 
Min. 
Max. 
255 
 
 
 
 
 
C.23 DefProg 
Initiates the default programming. 
0 x 
x
 
  
No Default programming 
Initiates Default programming 
 
 
 
 
 
1)
  actual value will not be changed during reset to default parameter 
2)
  on Controllers with Real-Time Clock, only 
3)
  can be overwritten by controller for self-adaption purposes, resolution = 0.01 K/min 
For detailed information of configuration parameters see chapter Configuration Settings
Table 4. Configuration parameters R7426A,B,C (part 2)