R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK 
 5 
EN1B-0203GE51 
R0507C 
 
control par. 
setting I / setting II 
R7426 
no.  name 
description 
low 
high  def. 
reso-
lution 
unit 
A  B C
actual 
value 
P.01 W1 
Main setpoint for input T1 
50 / 
130 
21 / 
70 
0.5 
°C x x x
 
P.02 Wlim 
Limit setpoint (low or high) for input T2 
5 /  
30 
50 / 
130 
16 / 
90 
°C x x x
 
P.03 Wcomp 
Compensation changeover point for input T3 
-5 
40 
20 
°C x x x
 
P.04 Wi 
Winter compensation authority -350 
+350
x x
 
P.05 Su 
Summer compensation authority -100 
+100
x x
 
P.06 Wcas 
Submaster or cascade setpoint 
OFF, 0 
50 
20 
0.5 
°C x x x
 
P.07 Rcas 
Cascade reset span adjustment 
40 
10 
0.5 
x  x x
 
P.08 Xp1 
Throttling range (main control loop) for T1 
0.5 
40 
0.5 
x  x x
 
P.09 Xp2 
Throttling range (cascade or limit control loop) 
for T2 
0.5 40 
10 
0.5 K 
x x
 
P.10 Xpc 
Cooling throttling range for sequence control 
OFF, 1 
40 
0.5 
  x x
 
P.11 Xph 
Heating throttling range for sequence control 
40 
0.5 
  x x
 
P.12 tr1
1)
 
Reset time (main control loop) 
OFF, 
20 sec 
20 
min 
OFF
10/ 
0.5 
sec/ 
min 
x x x
 
P.13 tr2
1)
 
Reset time (cascade control loop) 
OFF, 
20 sec 
20 
min 
OFF
10/ 
0.5 
sec/ 
min 
x x x
 
P.14 MINPOS 
Minimal pos. for air damper actuators 
50 
20 
  x x
 
P.15 Ystart 
Start point for mid range shift of output Y1 
-20 
+20 
0.5 
x  x x
 
P.16 SOFFS 
Offset of main setpoint in Standby mode 
10 
0.1 
x  x x
 
P.17 T1Cal 
Calibration of temperature sensor T1 
-20 
+20 
0.1 
x  x x
 
P.18 T2Cal 
Calibration of temperature sensor T2 
-20 
+20 
0.1 
x  x x
 
P.19 T3Cal 
Calibration of temperature sensor T3 
-20 
+20 
0.1 
x  x x
 
P.20 RetOffs 
Return air offset to simulate exhaust air cond. 
OFF, 0 
OFF
0.1 
  x x
 
P.21 RuntimeY1  Actuator run time for Y1 
180 
60 
sec  x  x
 
 
P.22 RuntimeY3  Actuator run time for Y3  
180 
60 
sec 
  x
 
 
P.23 RuntimeY2  Actuator run time for Y2  
180 
60 
sec 
  x
 
 
P.24 NightLow
2)
  Night low limit against temperature extremes 
OFF, 8 
19 
OFF
°C x x x
 
P.25 NightHigh
2)
  Night high limit against temperature extremes  OFF, 21
40 
OFF
°C x x x
 
P.26 NOFFS
2)
 
Offset of main setpoint in Night mode 
30 
0.1 
x  x x
 
1)
  for tr > 2 min  
⇒  resolution = 0.5 min, for tr < 2 min  ⇒  resolution = 10 sec 
2)
  on Controllers with Real-Time Clock, only 
For detailed information of control parameters see chapter Parameter Settings and Adjustment. 
Table 5. Control parameters R7426A,B,C