OPERATION IN EMERGENCY HEAT MODE
The balance point (outside) temperature is not used in the 
Emergency heat mode. When the thermostat is moved to the 
Emergency Heat position, the compressor is locked out. The 
first stage of heat is whatever is connected to the E terminal. 
The second stage of heat is what is connected to the Aux. 
terminal. Often there is only one source of non-compressor 
heat and the E terminal is jumped to the Aux. terminal.
Heat Pump with Electric Auxiliary (Backup) Heat and 
Outdoor Temperature Sensor
1. Choose correct heat pump application in Installer Setup 
Number 0170.
2. Choose Electric as Auxiliary (Backup) Heat Source in 
Installer Setup Number 0200.
3. Choose Outdoor Temperature Sensor for 
Control Option in Installer Setup Number 0340.
4. Choose Compressor Lockout Temperature in 
Installer Setup Number 0350.
5. Choose Auxiliary Lockout Temperature in Installer 
Setup Number 0360.
NOTE: There is a 5°F deadband between the Compressor 
and Auxiliary Heat Lockout Temperatures.
Operation in Heat Mode
When the outdoor temperature is below the Compressor 
Lockout Temperature, only the Auxiliary Heat operates.
When the outdoor temperature is above the Auxiliary Lockout 
Temperature, only the Compressor operates. See Fig. 34.
Fig. 34. Heat Pump Operation with Lockout 
Temperatures Set.
When the outdoor temperature is between the two 
temperatures, both the Compressor and Auxiliary Heat 
operate. 
Operation in Emergency Heat Mode
Once the thermostat is placed into the Emergency Heat 
mode, the compressor and auxiliary lockout features are 
turned off. In the Emergency heat mode, the compressor is 
locked out. The first stage of heat is whatever is connected to 
the E terminal. The second stage of heat is connected to the 
Aux. terminal. Usually the emergency and auxiliary heat 
sources are electric strip heat in these cases.
Operating Sequence
The thermostat energizes specific terminal(s), depending on 
the demand for heating, cooling or fan. The thermostat screen 
shows the time, inside temperature, system and fan 
selections. Additional indicators are shown when the heating, 
cooling or fan is energized. See Tables 9 - 11 for specification 
information.
a
G energizes only if Installer Setup number 0180 is set to Electric.
b
If Installer Setup System type is set to two stages of cooling.
c
If Installer Setup System type is set to two stages of heating.
35
M19950
COMPRESSOR
LOCKOUT
TEMPERATURE
AUXILIARY
LOCKOUT
TEMPERATURE
COMPRESSOR ONLY
BOTH COMPRESSOR AND
AUXILIARY HEAT
AUXILIARY ONLY
50
OUTDOOR TEMPERATURE
Table 9. Sequence of Operation for Conventional Systems.
System Setting
Fan Setting
Call for Action
Energize Terminals
Screen Message
Off
Auto
None
None
None
Cool
Auto
None
None
None
Cool or Auto
Auto
Stage 1 Cooling
Y, G
Cool On
Cool or Auto
Auto
Stage 1 and Stage 2 Cooling
Y, Y2
b
, G
Cool On
Heat
Auto
None
None
None
Heat or Auto
Auto
Stage 1 Heating
W, G
a
Heat On
Heat or Auto
Auto
Stage 1 and Stage 2 Heating
W, W2
c
, G
a
Heat On