Honeywell TH8320 Benutzerhandbuch

Seite von 40
VisionPRO
TM 
8000 Touchscreen Programmable Thermostat
35
68-0280—01
a
Configure O/B in Installer Setup. Based on last piece of equipment called (cooling = O or heating = B).
b
Red LED is on. See LED Indication section for more details.
c
If Installer Setup System Type is set to 2Heat/1Cool Heat Pump with Auxiliary Heat.
d
If Installer Setup System Type is set to 3Heat/2Cool Heat Pump with Auxiliary Heat.
e
This terminal does not energize if Installer Setup System type is set to 2 Heat/2 Cool Heat Pump with no Auxiliary Heat.
Second Stage Heat and Cool Control
While maintaining setpoint, several factors affect when 2nd 
stage energizes such as load conditions, environmental 
conditions, P+I control, and home insulation. The second 
stage energizes when the thermostat senses 1st stage is 
running at 90% capacity. This operation is droopless control.
Table 10. Sequence of Operation for Power Open and Power Closed Valves or Normally Open Valves.
System Setting
Fan Setting
Call for Action
Energize Terminals
Screen message
Off
N/A
 None
Y
None
Heat
N/A
None
Y
None
Heat
N/A
Heat
W
Heat On
Table 11. Sequence of Operation for Heat Pump Systems.
System Setting
Fan Setting
Call for Action
Energize Terminals
Screen message
Off
Auto
None
O/B
a
None
Cool
Auto
None
O/B
a
None
Cool or Auto
Auto
Stage 1 Cooling
Y, G, O/B
a
Cool On
Cool or Auto
Auto
Stage 1 and Stage 2 Cooling
Y,  Y2
d
, G, O/B
a
Cool On
Heat Auto
None
O/B
a
None
Heat or Auto
Auto
Stage 1 Heating
Y, G, O/B
a
Heat On
Heat or Auto
Auto
Stage 1 and Stage 2 Heating
Y, AUX
c
, G, O/B
a
Aux Heat On
Heat or Auto
Auto
Stage 1, 2 and 3 Heating
Y, Y2
d
, AUX
e
, G, O/B
a
Aux Heat On
Em. Heat
Auto
None
L
b
, O/B
a
None
Em. Heat
Auto
Stage 1 Heating
E, G, L
b
, O/B
a
Heat On
Em. Heat
Auto
Stage 1 and Stage 2 Heating
E, AUX, G, L
b
, O/B
a
Aux. Heat On