Honeywell 95-7769-01 Benutzerhandbuch

Seite von 176
WEBVISION™
95-7769—01
146
Fan Status
nvoData
FanOn
EnumPoint
Field No
nvoData
FieldNo
EnumPoint
Flow Sensor
nvoIO
siFlowSensorS3
NumericPoint
Flow Uncorrected
nvoIO
siFlowUncorrectedS3
NumericPoint
Flow Volts
nvoIO
siFlowVoltsS12
NumericPoint
Free 1 On
nvoData
Free1On
EnumPoint
Fresh Air Ratio
nvoData
siFreshAirRatio
NumericPoint
Heat Cool Switch
nvoData
HeatCoolSwitch
EnumPoint
Heat Cool Switch
nvoIO
HeatCoolSwitch
EnumPoint
Heat Stages
nvoData
HeatStages
NumericPoint
IO Test In
nvoIO
IOTestIn
EnumPoint
IO Test Switch
nvoIO
IOTestSwitch
EnumPoint
Low Flow Alarm
nvoData
LowFlowAlarm
EnumPoint
Manual Occupancy
nvoData
NetManOcc
EnumPoint
Mode
nvoData
Mode
EnumPoint
Model
nvoIO
Model
NumericPoint
Monitor Switch
nvoData
MonSwitch
EnumPoint
Monitor Switch
nvoIO
MonSwitch
EnumPoint
Occupancy Sensor
nvoIO
OccupancySensor
EnumPoint
Override
nvoData
OverRide
EnumPoint
Override IO
nvoIO
OverRide
EnumPoint
Peripheral Heat On
nvoData
PeriphHeatOn
EnumPoint
Peripheral Heat Position
nvoData
ubPeriphHeatPosS1
NumericPoint
Reheat Percentage
nvoData
ubReheatPosS1
NumericPoint
Scheduled Occupancy
nvoData
SchedOcc
EnumPoint
Sensor Occupancy
nvoData
SenOcc
EnumPoint
Space Temperature
nvoData
siSpaceTempS7
NumericPoint
Space Temperature IO
nvoIO
siSpaceTempS7
NumericPoint
Supply Temperature
nvoData
siSupplyTempS7
NumericPoint
Temperature Sensor 0
nvoIO
siTempSensorS7N0
NumericPoint
Temperature Sensor 1
nvoIO
siTempSensorS7N1
NumericPoint
Temperature Setpoint
nvoData
siTempControlPtS7
NumericPoint
Window Open
nvoData
WindowOpen
EnumPoint
Window Open IO
nvoIO
WindowOpen
EnumPoint
Table 86. VAV II Point Details. (Continued)
Point Name
Network Variable
Field
Point Type
Table 87. VAV II Application of Points
Point Name
Graphics Alarms Trends Commandable Internal Use
Valid Values
Occupied Cool (Setpoint)
X
 Units=ºC
 Precision=2
 Min=10.0
 Max=35.0
Standby Cool (Setpoint)
X
 Units=ºC
 Precision=2
 Min=10.0
 Max=35.0