Honeywell 95-7769-01 Benutzerhandbuch

Seite von 176
WEBVISION™
147
95-7769—01
Unoccupied Cool (Setpoint)
X
 Units=ºC
 Precision=2
 Min=10.0
 Max=35.0
Occupied Heat (Setpoint)
X
 Units=ºC
 Precision=2
 Min=10.0
 Max=35.0
Standby Heat (Setpoint)
X
 Units=ºC
 Precision=2
 Min=10.0
 Max=35.0
Unoccupied Heat (Setpoint)
X
 Units=ºC
 Precision=2
 Min=10.0
 Max=35.0
Current State
X
 Default
 Occupied
 Unoccupied
 Bypass
 Standby
Next State
X
 Default
 Occupied
 Unoccupied
 Bypass
 Standby
Time To Next State
X
 Units=min
 Precision=0
 Min=0.0
 Max=65535.0
DLC Shed
X
 dlNoDlcShed
 dlMinDlcShed
Communication Failed
X
 False or True
Frost Protect
X
 False or True
Invalid Config
X
 False or True
Invalid Setpoint
X
 False or True
Node Disabled
X
 False or True
Sensor Failed
X
 False or True
Smoke Emergency
X
 False or True
Table 87. VAV II Application of Points (Continued)
Point Name
Graphics Alarms Trends Commandable Internal Use
Valid Values