1.  1 square inch per 3000 Btu/hr (700 mm
2
 per kW) of the total 
input rating of all appliances located in the enclosure, and
2.  Not less than the sum of the areas of all vent connectors in the space.
outdoor aIr throuGh two horIZontal ducts
fIGure 6.
The confined space shall be provided with two permanent horizontal 
ducts, one commencing within 12 inches (300 mm) of the top and 
one commencing within 12 inches (300 mm) of the bottom of the 
enclosure. The horizontal ducts shall communicate directly with the 
outdoors. See Figure 6.
Each duct opening shall have a minimum free area of 1 square inch 
per 2,000 Btu/hr (1100 mm
2
 per kW) of the aggregate input rating of 
all appliances installed in the enclosure.
When ducts are used, they shall be of the same cross sectional area 
as the free area of the openings to which they connect. The minimum 
dimension of rectangular air ducts shall be not less than 3 inches.
aIr froM other Indoor spaces
fIGure 7.
The  confined  space  shall  be  provided  with  two  permanent 
openings, one commencing within 12 inches (300 mm) of the top 
and one commencing within 12 inches (300 mm) of the bottom of 
the enclosure. See Figure 7.
Each opening shall communicate directly with an additional room(s) 
of  sufficient  volume  so  that  the  combined  volume  of  all  spaces 
meets the criteria for an Unconfined Space.
Each opening shall have a minimum free area of 1 square inch per 
1,000 Btu/hr (1100 mm
2
 per kW) of the aggregate input rating of all 
appliances  installed in the enclosure.  Each opening  shall  not be 
less than 100 square inches (645 cm
2
).