TERMINATION CLEARANCES SIDEWALL DIRECT VENT
V
X
VENT TERMINAL
AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
v
v
A
G
V
FIXED
CLOSED
FIXED
CLOSED
OPERABLE
OPERABLE
V
C
B
B
B
B
F
B
V
V
A
J
V
H
M
X
X
V
V
K
B
E
D
L
DIRECT VENT
(using outdoor air for combustion)
EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION
Figure: 16
Vent terminal clearances for “Direct Vent” installations. Direct Vent configurations use outdoor air for combustion.
US INSTALLATIONS 1
US INSTALLATIONS 1
A
Clearance above grade, 
veranda, porch, deck or 
balcony
12 inches (30 cm)
H
Clearance to each side 
of center line extended 
above meter/regulator 
assembly
3 feet (91 cm) within a height 
15 feet (4.5 m) above the 
meter/regulator assembly*
B
Clearance to window or 
door that may be opened
6 inches (15 cm) 
for appliances up to 
10,000 Btu/hr (3 kW), 
9 inches (23 cm) for 
appliances between 
10,000 Btu/hr (3 kW) 
and 50,000 Btu/hr (15 
kW), 12 inches (30 cm) 
for appliances above 
50,000 Btu/hr (15 kW)
I
Clearance to service 
regulator vent outlet
3 feet (91 cm)*
C
Clearance to 
permanently closed 
window
6 inches (15 cm)*
J
Clearance to a non 
mechanical air supply 
inlet into building or 
combustion air inlet to 
any other appliance
6 inches (15 cm) for 
appliances up to 10,000 
Btu/hr (3 kW), 9 inches (23 
cm) for appliances between 
10,000 Btu/hr (3 kW) and 
50,000 Btu/hr (15 kW), 12 
inches (30 cm) for appliances 
above 50,000 Btu/hr (15 kW)
D
Vertical clearance to 
ventilated soffit located 
above the terminal within 
a horizontal distance of 
2 feet (61 cm) from the 
center line of the terminal
12 inches (30 cm)*
K
Clearance to a 
mechanical air supply 
inlet
3 feet (91 cm) above if within 
10 feet (3 m) horizontally
E
Clearance to unventilated 
soffit
12 inches (30 cm)*
L
Clearance above 
paved sidewalk or 
paved driveway located 
on public property
7 feet (2.13 m)†*
F
Clearance to outside 
corner
2 feet (60 cm)*
M
Clearance under 
veranda, porch, deck, 
or balcony
12 inches (30 cm) ‡*
G
Clearance to inside 
corner
18 inches (45 cm)*
1 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
† A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.