Delta DTD Series Benutzerhandbuch

Seite von 7
 
Http://www.delta.com.tw/industrialautomation
 
 
 
Series Temperature Controller Instruction Sheet
 
Thank you very much for choosing Delta DTD series temperature controller. Please read this instruction sheet before using your DTD to ensure proper 
operation. Keep this instruction sheet handy for quick reference. 
 
Warning
 
 
DANGER! CAUTION! ELECTRIC SHOCK! When the power is on, DO NOT touch the AC terminals in case an electric shock may occur. Make sure 
the power is disconnected when you check the input power.   
 
DTD is an OPEN-TYPE device. If it will cause serious injury to workers or damage on other equipments when used in a dangerous environment, 
please make sure it is installed in an automatic safety protection device.   
1.  Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, Max. width 7.2mm). Please be sure to tighten 
them properly and make sure the wire is connected to the correct terminal.   
2.  Prevent dust or metallic debris from falling into the device and cause malfunctions. DO NOT modify or uninstall DTD series without 
being permitted. DO NOT use empty terminals.   
3.  Keep away from high-voltage and high-frequency environment during installation in case of interference. Prevent using the device in 
premises which contain:     
(a) dust or corrosive gas; (b) high humidity and high radiation; (c) shock and vibration 
4.  The power has to be switched off when wiring or changing temperature sensor. 
5.  Make sure to use compensation wire which matches the thermocouple when extending or connecting the thermocouple wire.   
6.  Use wires with resistance when extending or connecting the platinum resistance sensor. 
7.  Keep the wire as short as possible when wiring a sensor to the temperature controller. Separate the power cable and load wire in 
order to prevent interference and induced noise. 
8.  DTD is an open-type device. Make sure to install it in an enclosure which prevents dust and humidity in case of an electric shock.  
9.  Make sure the power cables and signal device are installed correctly before switching on the power; otherwise serious damage may 
occur. 
10. DO NOT touch the terminals or repair the device when the power is on; otherwise an electric shock may occur 
11. Please wait for one minute after the power is switched off to allow the capacitor to discharge and DO NOT touch the internal wiring 
within this period. Use dry cloth to clean the device. DO NOT use acid or alkaline liquid to clean the device. 
 
 
Display, LED & Pushbuttons 
PV 
Present value/function display
(red 7-segment LED) 
SV 
Set value 
(green 7-segment LED) 
AT 
Flashes when PID auto-tuning
(green LED) 
OUT 
On when output (green LED) 
ALM 
On when alarm (red LED) 
 
Selecting modes 
completing setup 
 
Displaying functions 
Left-shifting the digit 
 
Ordering Information 
DTD
0
1 2 3 4 5
 
 
Series name 
DTD: Delta D series temperature controller 
1
!
 
Up key 
 
2 3 4
 
Panel size   
(W × H) 
4848: 1/16 DIN W48 × H48 mm 
4896: 1/8 DIN W48 × H96 mm 
7272: W72 × H72 mm 
5
 
R: Relay output SPST (250VAC, 5A) 
V: Voltage pulse output 14V +10% ~ -20%   
(Max. 40mA) 
Optional 0: 
None 
 
 
Specifications
 
Power input 
AC100 ~ 240V 50/60Hz 
Input power range 
85% ~ 110%, rated voltage 
Power consumption 
6VA Max. 
Display 
7-segment LED; PV in red, SV in green 
Input temperature 
sensor 
Thermocouple: K, J, T, E, N, R, S, B, U, L, Txk 
Platinum resistance: Pt100, JPt100 
Copper resistance: Cu50 
Analog input 
Current: 0 ~ 20mA, 4 ~ 20mA 
Voltage: 0 ~ 5V, 0 ~ 10V, 0 ~ 70mV 
Display scale 
For temperature input: K2, J2, T2, Pt100-2, JPt100 and Cu50 can display to 0.1 degree; others display in 
1degree as a unit. 
Control method 
PID, PID programmable control, On/Off, manual output 
Relay output: AC 250V, 5A, SPST 
Control output type 
Voltage pulse output: DC 14V, Max. output current 40mA 
Sampling cycle 
0.4 second (including analog input signal and sensor input signal) 
Vibration resistance 
10 ~ 55Hz 10m/s
2  
3 axes 10mins 
Shock resistance 
Max. 300m/ s
2
    3 axes 6 directions, 3 times each 
Ambient temperature 
0°C ~ 50°C 
 
1