Delta DTD Series Benutzerhandbuch

Seite von 7
 
Input Sensor Type 
Display 
Temperature Range 
0V ~ 5V input 
 
-999 ~ 9,999 
0 ~ 70mV input 
 
-999 ~ 9,999 
Cu50 type 
 
-50
 o
C ~ 150
 o
C (-90.0
 o
F ~ 302.0
 o
F) 
Pt100 type 2 
 
-99.9
o
C ~ 600.0
o
C (-99.9
o
F ~ 999.9
o
F) 
Pt100 type 1 
 
-200
o
C ~ 600
o
C (-360
o
F ~ 1,112
o
F) 
JPt100 type 
 
-20.0
o
C ~ 400.0
o
C (-36.0
o
F ~ 752.0
o
F) 
Thermocouple TXK type 
 
-200
o
C ~ 800
o
C (-360
o
F ~ 1,472
o
F) 
Thermocouple U type 
 
-200
o
C ~ 500
o
C (-360
o
F ~ 932
o
F) 
Thermocouple L type 
 
-200
o
C ~ 850
o
C (-360
o
F ~ 1,562
o
F) 
Thermocouple B type 
 
100
o
C ~ 1,800
o
C (180
o
F ~ 3,272
o
F) 
Thermocouple S type 
 
0
o
C ~ 1,700
o
C (0
o
F ~ 3,092
o
F) 
Thermocouple R type 
 
0
o
C ~ 1,700
o
C (0
o
F ~ 3,092
o
F) 
Thermocouple N type 
 
-200
o
C ~ 1,300
o
C (-360
o
F ~ 2,372
o
F) 
Thermocouple E type 
 
0
o
C ~ 600
o
C (0
o
F ~ 1,112
o
F) 
Thermocouple T type 2 
 
-99.9
o
C ~ 400.0
o
C (-99.9
o
F ~ 752.0
o
F) 
Thermocouple T type 1 
 
-200
o
C ~ 400
o
C (-360
o
F ~ 752
o
F) 
Thermocouple J type 2 
 
-99.9
o
C ~ 999.9
o
C (-99.9
o
F ~ 999.9
o
F) 
Thermocouple J type 1 
 
-200
o
C ~ 1,200
o
C (-360
o
F ~ 2,192
o
F) 
Thermocouple K type 2 
 
-99.9
o
C ~ 999.9
o
C (-99.9
o
F ~ 999.9
o
F) 
Thermocouple K type 1 
 
-200
 o
C ~ 1,300
o
C (-360
o
F ~ 2,372
o
F) 
 
Control Settings!
 Setting up Control Mode 
In the operation mode, press 
  for more than 3 seconds and PV will display the parameter 
. Press 
  for 4 times to display 
the parameter 
. The default setting of this parameter is “On/Off control” 
. Use 
  to select PID control 
, PID 
programmable control 
  or manual control 
. Press 
  again and display the parameter 
  for selecting the control 
method. You can select heading (default) 
 or cooling 
. Press 
  to return to the operation mode. 
 Setting up RUN and STOP   
In the operation mode, press 
 and display parameter 
. The default is RUN 
. Use 
  to select STOP 
. Press 
  to complete the setting and the output will be disabled. 
 Setting up On/Off Control Parameters 
Press 
  in the operation mode. If DTD is in On/Off heating mode, the PV will display 
; if in On/Off cooling mode, the PV will 
display 
. Modify these parameters to set up the hysteresis of On/Off. The default setting is 0 (without hysteresis). When the output 
reaches SV, the control output will be disabled. When the input is bigger (cooling) or smaller (heating) than the SV and hysteresis, the 
control output will be enabled. When the On/Off hysteresis is not 0, the control output will be like the diagrams below. 
 
 
Hysteresis
HtS
OFF
ON
OFF
ON/OFF Control for Heating
SV
     
Hysteresis
CtS
OFF
ON
ON
ON/OFF Control for Cooling
SV
 
 
 Setting up PID Parameters 
When in PID control mode, you have to first decide the On/Off cycle time for the control output, i.e. the control cycle. Press 
 in the 
operation mode and PV will display 
. Press 
  5 times to display the parameters of heating control cycle 
 or cooling 
control cycle 
. Set up the cycle depending on the reaction speed of the control system. In principle, the faster the reaction, the 
shorter the cycle and more accurate the control. A short control cycle indicates that there will be more times of On/Off. If you adopt relay 
output, the short cycle will shorten the life span of the relay. Therefore, it is recommended that you adopt voltage output in the PID control 
mode. The default setting of the control cycle is 20 seconds.   
 
3