Multiquip DCA220SSCU4i Benutzerhandbuch

Seite von 90
page 18 — dca220sscu/4i 60 hz generaTor • operaTion and parTs manual — rev. #0 (10/25/12) 
eNGiNe CONtrOL UNit (eCU)
Figure 4. Engine Control Unit (ECU)
PSI
OIL PRESS
0
25
50
75
100
°F
WATER TEMP
100
140
180
220
260
VOLTS
BATTERY
6
12
18
24
30
°F
FUEL
E
½
F
RPMX10
SPEED
0
120
150
180
210
60
Series 800 Controller
ECU
Engine Started
Shutdown
Pre-Alarm
Alarm
Acknowledge
Screen
Change
Program
Exit
Option
OFF
U-V
W-U
V-W
OFF
V
W
U
INCREASE
DECREASE
Series 800 Controller
ECU
Engine Started
Shutdown
Pre-Alarm
Alarm
Acknowledge
Screen
Change
Program
Exit
Option
A
B
C
D
E
F G
H
1
The definitions below describe the controls and functions 
of the Engine Control Unit (Figure 4).
1. 
ecu  controller  — This  auto  start/stop  controller 
displays  the  parameters  and  the  diagnostic 
troubleshooting messages of the engine, and controls 
DPF regeneration.
A. 
ecu display screen — Engine fault diagnostic  
messages are shown on this LCD display. screen
B. 
engine  started  lamp  — This  lamp  when  lit 
indicates engine is operating normally.
C. 
engine  shutdown  lamp  — When  an  engine 
failure has occured this lamp will blink. Indicating 
the  engine  has  been  shutdown. The  diagnostic 
fault message will be displayed on the LCD screen.
D. 
pre alarm lamp — When an engine failure has 
occured this lamp will blink. Indicating a pre-fault 
engine  condition  and  the  possibility  of  engine 
shutdown.The  diagnostic  fault  message  will  be 
displayed on the LCD screen
E. 
alarm acknowledge Button — When the engine 
experiences a fault, the "Pre Alarm Lamp" or the 
"Shutdown Lamp" will start blinking. Pushing this 
button  will  confirm  the  fault  message  and  the 
blinking lamp will change to a solid lamp display. 
The fault message will be displayed on the screen. 
When multiple engine faults occur, the lamp will 
continue  blnking  until  all  fault  messages  are 
confirmed. The blinking lamp will change to a solid 
lamp display all current confirmed fault messages 
will scrool across the screen. 
F. 
screen change Button — When this button is 
pushed  during  operation,  the  screen  will  cycle 
through each parameter screen.
G. 
option Button  — This button is not active. Do 
not use.
H. 
program/exit  Button  —  Pushing  this  button 
allows the DPF Force Regen and diagnostic code 