dca220sscu/4i 60 hz generaTor• operaTion manual — rev. #0 (10/25/12) — page 19
eNGiNe/GeNeratOr CONtrOL paNeL
The definitions below describe the controls and functions 
of the Engine/Generator Control Panel (Figure 5).
1. 
gauge  unit  assembly  —   This  assembly  houses 
the various engine monitoring gauges. These gauges  
indicate:  oil  pressure,  water  temperature,  charging 
voltmeter, fuel and engine speed RPM (tachometer).
A. 
oil pressure gauge — During normal operation 
this gauge be should read between 35 to 65 psi. 
(241~448 kPa). When starting the generator the 
oil pressure may read a little higher, but after the 
engine warms up the oil pressure should return to 
the correct pressure range.
B. 
Water Temperature  gauge  —  During  normal 
operation this gauge be should read between 180° 
and 225°F (82°~107°C).
C. 
charging voltmeter  gauge  —  During  normal 
operation this gauge indicate minimum 26 VDC
D. 
Fuel gauge — Indicates amount of diesel fuel 
available.
E. 
Tachometer — Indicates engine speed in RPM’s 
for 60 Hz operation. This meter should indicate 
1800 RPM’s when the rated load is applied. .
2. 
panel  light  —  For  operation  at  night,  panel  light 
illuminates control panel for ease of reading meters 
and gauges. Make sure oanel light switch is in the OFF 
position when light is not in use.
3. 
panel light switch — When activated will turn on 
control panel light.
4. 
Frequency meter — Indicates the output frequency 
in hertz (Hz). Normally 60 Hz
PSI
OIL PRESS
0
25
50
75
100
°F
WATER TEMP
100
140
180
220
260
VOLTS
BATTERY
6
12
18
24
30
°F
FUEL
E
½
F
RPMX10
SPEED
0
120
150
180
210
60
D
A
B
C
E
1
PSI
OIL PRESS
0
25
50
75
100
°F
WATER TEMP
100
140
180
220
260
VOLTS
BATTERY
6
12
18
24
30
°F
FUEL
E
½
F
RPMX10
SPEED
0
120
150
180
210
60
Series 800 Controller
ECU
Engine Started
Shutdown
Pre-Alarm
Alarm
Acknowledge
Screen
Change
Program
Exit
Option
OFF
U-V
W-U
V-W
OFF
V
W
U
INCREASE
DECREASE
7
4
5
6
8
9
10
11
13
12
2
3
14
Figure 5. Gauge Unit Assembly
5. 
ac ammeter — Indicates the amount of current the 
load is drawing from the generator per leg selected by 
the ammeter phase-selector switch.
6. 
ac voltmeter — Indicates the output voltage present 
at the 
u,v, and W output Terminal lugs.
7. 
voltage regulator control — Allows ±15% manual 
adjustment of the generator’s output voltage.
8. 
ammeter change-over switch — This switch allows 
the AC ammeter to indicate the current flowing to the load 
connected to any phase of the output terminals, or to be 
switched off. This switch does not effect the generator 
output in any fashion, it is for current reading only. 
9. 
voltmeter change-over switch — This switch allows 
the AC voltmeter to indicate phase to phase voltage 
between any two phases of the output terminals or to 
be switched off.
10. 
emergency stop Button — Push this button inward 
to stop the engine in the event of an emergency. 
do 
noT use this button as a means of stopping the engine. 
11. 
engine  speed  switch  — This  switch  controls  the 
speed of the engine (low/high).
12. 
auto/start switch — This switch selects either manual 
or automatic operation . Center position is OFF (reset).
13. 
hour check Button — With the engine stopped, press 
and hold ths button. The total running hours, fuel level, 
and battery voltage will be displayed.
14. 
main circuit Breaker  — This three-pole, 600 amp 
main breaker is provided to protect the 
u,v, and W 
output Terminal lugs from overload.