Hitachi SJ300-037HFE Benutzerhandbuch
SJ300 Inverter
T
roub
leshooting
and Maintenance
6–7
NOTE: If an EEPROM error (E08) occurs, be sure to confirm the parameter data values are
still correct.
still correct.
E23
Gate array error
An internal inverter error has occurred in commu-
nications between the CPU and gate array IC.
nications between the CPU and gate array IC.
E24
Phase failure detection
One of three lines of the 3-phase power is missing.
E30
IGBT error
When an instantaneous over-current condition
occurs on any IGBT (output transistor) device, the
inverter alarm trips. then it turns the outputs OFF
in order to protect the circuitry.
occurs on any IGBT (output transistor) device, the
inverter alarm trips. then it turns the outputs OFF
in order to protect the circuitry.
E35
Thermistor
When a thermistor is connected to terminals [TH]
and [CM1] and the inverter has sensed the temper-
ature is too high, the inverter trips and turns OFF
the output.
and [CM1] and the inverter has sensed the temper-
ature is too high, the inverter trips and turns OFF
the output.
E36
Brake error
When the inverter releases the brake and cannot
detect whether the external brake is ON or OFF
within the waiting time (set by parameter B024),
the inverter trips and turns OFF the output to the
motor.
detect whether the external brake is ON or OFF
within the waiting time (set by parameter B024),
the inverter trips and turns OFF the output to the
motor.
––––
Under-voltage (brownout)
with output shutoff
with output shutoff
Due to low input voltage, the inverter turns its
output OFF and tries to restart. If it fails to restart,
then the alarm trips to record the under-voltage
error event.
output OFF and tries to restart. If it fails to restart,
then the alarm trips to record the under-voltage
error event.
Automatic restart and phase
loss
loss
The inverter is restarting, due to an over-current,
over-voltage, under-voltage, or a phase loss event.
See parameter B001 setting in
over-voltage, under-voltage, or a phase loss event.
See parameter B001 setting in
.
E6X
Expansion card #1
connection error
connection error
An error has occurred in an expansion card or at
its connecting terminals. Please refer to the
manual for the expansion card for additional
details.
its connecting terminals. Please refer to the
manual for the expansion card for additional
details.
E7X
Expansion card #2
connection error
connection error
Error
Code
Name
Probable Cause(s)