FieldServer FS-8700-83 Benutzerhandbuch

Seite von 24
FS-8700-83 Gamewell 
 
 
 
 
 
 
 
 
Page 3 of 24 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldserver.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldserver.com 
4.  Configuring the FieldServer as a Gamewell Serial Driver Client 
For a detailed discussion on FieldServer configuration, please refer to the FieldServer 
Configuration Manual. The information that follows describes how to expand upon the factory 
defaults provided in the configuration files included with the FieldServer (See “.csv” files on the 
driver diskette). 
 
This section documents and describes the parameters necessary for configuring the FieldServer 
to communicate with a Gamewell Serial Driver Server 
 
The configuration file tells the FieldServer about its interfaces, and the routing of data required. 
In order to enable the FieldServer for Gamewell Serial Driver communications, the driver 
independent FieldServer buffers need to be declared in the “Data Arrays” section, the 
destination device addresses need to be declared in the “Client Side Nodes” section, and the 
data required from the servers needs to be mapped in the “Client Side Map Descriptors” 
section. Details on how to do this can be found below. 
 
Note that in the tables,  * indicates an optional parameter, with the bold legal value being the 
default. 
4.1 Data  Arrays 
Section Title 
Data_Arrays 
Column Title 
Function 
Legal Values 
Data_Array_Name 
Provide name for Data Array 
Up to 15 alphanumeric 
characters 
Data_Format 
Provide data format. Each data array can 
only take on one format. 
FLOAT, BIT, UInt16, SInt16, 
Packed_Bit, Byte, 
Packed_Byte, 
Swapped_Byte 
Data_Array_Length 
Number of Data Objects. Must be larger 
than the data storage area required for 
the data being placed in this array. 
1-10,000 
 
 
 
Example 
 
//    Data Arrays 
// 
Data_Arrays 
Data_Array_Name,  Data_Format,  
Data_Array_Length 
DA_AI_01,         UInt16,       
 
200 
DA_AO_01,         UInt16,       
 
200 
DA_DI_01,         Bit,          
 
200 
DA_DO_01,         Bit,          
 
200