4.3 Client Side Nodes 
 
Section Title 
Nodes 
Column Title 
Function 
Legal Values 
Node_Name 
Provide name for node 
Up to 32 alphanumeric 
characters 
Node_ID 
Gamewell panel node address. 
 
 
The Node Id has no meaning 
when the FieldServer is 
connected directly to Gamewell 
panel.  When connecting to a 
Gamewell panel directly always 
set the Node_ID to zero. When 
connecting to a Gamewell 
SmartNet terminal. The 
Node_ID is important and 
should correspond to the 
Node_ID’s of the panel’s 
connected to the SmartNet 
terminal. 
 
0-256 
Protocol 
Specify protocol used 
Gamewell 
Port 
Specify which port the device is 
connected to the FieldServer. 
 
The use of R1 and R2 is only 
appropriate when a 232/485 
converter is used. The 
Gamewell panels only have a 
232 port available for 
connection. 
P1-P8, R1-R2 
 
Example 
 
//    Client Side Nodes 
 
Nodes 
Node_Name, Node_ID, Protocol, Port 
Panel1   , 0      , Gamewell, P8