GE 68K System Benutzerhandbuch

Seite von 112
68K System Monitor
User's Guide
GE Energy Services
General
SWM0023-1.00 -2
Full Release
3-79
TR - Trace
Platform
o
CPM
o
D20
D20 Base
o
D20 ME
D20 Base
o
D20/200
CCU Base
o
D20/200 ME
CCU Base
o
D25
Description
Use this command to track the execution sequence of the processes in the system.
Syntax
Below is usage and syntax information for this command
Command Format
tr [/h | /c | /s]
tr /d [/c] [/e] [<start_time> [<end time>] ]
tr /r [/g] [<samples>] /t0 <pre_trigger> <address> <condition>
<value>
tr /r [/g] [<samples>] /t1 <pre_trigger> <trigger time>
tr /r [/g] [<samples>] /t2 <pre_trigger> <process name>
Variables
/h
= display help
/c
= clear all
/s
= stop collection
/d
= display gathered data
/c – continuous display,
/e – format for spread sheets
/r
= gather data
/g
= allocate buffers from global memory
Parameters
start_time
= start time for trace to display.
end time
= end time for trace to display.
pre_trigger
= number of samples to store before the trigger
address
= the watch  address to trigger on
condition
= Condition to watch for  =  !=  <  >  <=  >=
change
value
= value to watch for
trigger time = RTC time to trigger
process name = name of process to trigger on