Appendix – Re-Assembly Procedure 
 
7
Auxiliary Connection 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 2 : Motor Contactor Connections 
9.  Using a flat screwdriver, 3mmx100mm 
(1/8”x4”), torque the following auxiliary 
terminals to 2.0 N-m (17.5 in-lbs) on the 
right side of the motor contactor.  See 
Figure 28 for location of auxiliaries. 
Wire Number 
AJ9CC1-2 31 
AJ9CC1-4 32 
 
 
 
8
7
Torque the motor terminals and ground 
terminals to 31.0 N-m (275 in-lbs) using a 
8mm (5/16”) Allen hex key.   
Tie wrap the two rubber boots to the output 
terminal blocks A1 and A2 after wiring the 
motor armature. 
 
 
 
 
 
 
 
 
 
 
 
Figure 2 : Right side of Motor Contactor 
10.  For Motor Armature Connections, place 
rubber boots over wires first, then connect 
those appropriately sized wires from the 
motor armature directly to the motor 
contactor (ME) compression lug terminals 
(1) and (3).  Also connect a properly sized 
frame to t ground continuity wire from the 
motor he PE grounding terminal on the 
Motor Side drive panel.  See EMC 
Compliance on page 9 . 
26  25  16  19 
TB2-1
To motor 
contactor 
11.  Finally, connect the incoming 3-phase 
power wires and PE building ground to the 
main power terminals at the top of the Line 
Side Converter enclosure.  View Figure 29 
for locations of terminals. 
Use the following torque specs when 
tighten the screws and lugs down: 
Wire References 
Torque Specs 
Power Terminals 
56.6 N-m (500 in-lbs) 
Plastic Cover Screws 
0.23-0.28 N-m (2-2.5 in-lbs) 
Ground Terminals 
31.0 N-m (275 in-lbs) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
9
Incoming 
Power 
Terminals
Grounding
lug 
Plastic 
Safety 
Cover 
#A9JCC1-2 to 31 
#A9JCC1-2 to 32 
 
 
 
 
 
 
 
 
Figure 2 : Power Terminals 
 
 
 
 
 
 
 