Quattro DC Drive Parameters A1 
 
 
Adjust A0 menu 
Drive A1 submenu 
Parameter Description 
Units 
Default Range 
Hidden
Item 
Run 
lock
out
fpm 
400.0 
0.0 – 1500.0 
CONTRACT 
CAR SPD 
(Contract Car Speed)
 
Adjusts the elevator 
contract speed in feet per minute (fpm) or 
meters per second (m/s). 
 
m/s 
2.000 
0.00 – 8.00 
N Y 
CONTRACT 
MTR SPD  
(Contract Motor Speed) 
 
Sets motor rpm 
when commanded to run at elevator 
contract speed.  The speed regulator 
actually regulates RPM x Encoder PPR 
pulses per second.  Trim this value to fine 
tune actual elevator speed. 
rpm 
1130.0 
30.0 – 3000.0 
N Y 
RESPONSE  
(Response) 
 
Sets the sensitivity of the 
drive’s speed regulator in terms of the 
speed regulator bandwidth in radians.  The 
responsiveness of the drive as it follows 
the speed reference will increase as this 
number increases.  If the number is too 
large, the motor current and speed will be 
jittery.  If this number is too small, the 
motor will be sluggish. 
rad/sec
10.0 
1.0 – 20.0 
N N 
INERTIA 
(Per Unit System Inertia) This parameter is 
the inertia/torque ratio as seen by the 
drive.  It affects internal gain of the speed 
regulator.  This time in seconds is the time 
it would take the motor to accelerate a 
load-balanced elevator to contract speed 
at rated torque. 
sec 
2.00 
0.25 – 50.00 
N N 
INNER LOOP 
XOVER 
(Inner Loop Crossover) 
 
This parameter is 
used as a stiffness factor.  Higher settings 
make the drive more responsive to load 
changes and can help minimize rollback.  
Because of the amount of responsiveness 
due to a high setting, the drive is more 
sensitive to speed disturbances and this 
parameter can affect ride quality.  Note: 
this parameter is only used when SPEED 
REG TYPE (C1) = ELEV SPD REG.  See 
SPD PHASE MARGIN (A1) if using PI 
REG. 
rad/sec
2.0 
0.1 – 20.0 
N N 
CURRENT 
LIMIT 
(Armature Current Limit) 
 
This parameter 
sets armature current limit for DC motor 
applications. 
200.0 
0.0 – 275.0 
N N 
GAIN REDUCE 
MULT 
(Gain Reduce Multiplier) 
 
This parameter 
is the percent of ‘response’ the speed 
regulator should use in the ‘low gain’ 
mode.  This value reduces the 
RESPONSE value when the drive is in 
‘low gain’ mode.  (i.e. setting this 
parameter to 100% equals no reduction in 
gain in the ‘low gain’ mode) 
100 
10 – 100 
Y N 
GAIN CHNG 
LEVEL 
(Gain Change Level)   
W
hen the HI/LO 
GAIN SRC in submenu C1 is set to 
internal, the drive will control the high/low 
gain switch.  This parameter sets the 
speed reference level, above which, the 
drive is in ‘low gain’ mode.  Units in 
percent of rated speed. 
For more information, see GAIN CHNG 
LEVEL on page 36.
 
100.0 
0.0 – 100.0 
Y N 
30