Quattro DC Logic Inputs C2 Submenu 
 
Logic Inputs C2 submenu 
(Logic Inputs 1-9) 
This parameter defines the function of the logic 
inputs.   
NOTE: The user can assign particular 
functions to each input terminal. Only one 
function per terminal is allowed and multiple 
terminals cannot have the same function 
(except “No Function”).  When a function is 
assigned to an input terminal, it is removed 
from the list of possible selections for 
subsequent terminals.  To re-assign a 
function to a different terminal one must 
first assign “No Function” to the original 
terminal so that the desired function is 
returned to the list of selections and can be 
assigned to a different new terminal. 
 
NOTE:  The current setting of each parameter 
is displayed in all caps; all other choices in the 
list are displayed in lower case.
 
Parameter Description 
Default 
Hidden 
Item 
Run 
lock
out 
N.C. INPUTS 
(Normally Closed Inputs) All Logic Inputs may 
be configured for use with Normally Open or 
Normally Closed external contacts.  The 
numeric entry is a hexadecimal 
representation of a binary control bit for each 
channel.  A binary 0 means Normally Open.  
A binary 1 indicates a Normally Closed 
external switch.  Logic Input #1 is the least 
significant bit.  The defaulted value of 0001 
indicates logic input 1 is normally closed. 
 
 
Binary 0000, 0000, 0000, 0000 
 
 
See table below for converting binary to hex: 
Bit 3 
Bit 2 
Bit 1 
Bit 0 
Hex 
0 0 0 0 0 
0 0 0 1 1 
0 0 1 0 2 
0 0 1 1 3 
0 1 0 0 4 
0 1 0 1 5 
0 1 1 0 6 
0 1 1 1 7 
1 0 0 0 8 
1 0 0 1 9 
1 0 1 0 A 
1 0 1 1 B 
1 1 0 0 C 
1 1 0 1 D 
1 1 1 0 E 
1 1 1 1 F 
 
0001 Y 
LOGIC INPUT 1 TB1(1) 
logic input #1   note: drive comes pre-wired 
for logic input #1 to be CONTACT CFIRM 
CONTACT CFIRM 
Y Y 
LOGIC INPUT 2 TB1(2) 
logic input #2   note: drive comes pre-wired 
for logic input #2 to be CTR PWR SENSE 
CTR PWR SENSE 
LOGIC INPUT 3 TB1(3) 
logic input #3 
NO FUNCTION 
LOGIC INPUT 4 TB1(4) 
logic input #4 
DRIVE ENABLE 
LOGIC INPUT 5 TB1(5) 
logic input #5 
RUN 
LOGIC INPUT 6 TB1(6) 
logic input #6 
UP/DWN 
LOGIC INPUT 7 TB1(7) 
logic input #7 
STEP REF B0 
LOGIC INPUT 8 TB1(8) 
logic input #8 
STEP REF B1 
LOGIC INPUT 9 TB1(9) 
logic input #9 
FAULT RESET 
Logic Input #1
Logic Input #9
most significant 
byte 
least significant 
byte 
 
61