Chapter 2 - Connections 
 
 
This chapter will cover the connections required for the 
485SDD16.  There are three sets of connections:  digital I/O, serial 
port, and power supply. Do not make any connections to the 
485SDD16 until you have read this chapter.   
 
Digital I/O Connections 
 
Connections to the I/O lines are made through the DB25S 
(female) I/O port connector.  Refer to Table 2.1.  See Chapter 5 for 
I/O interfacing examples. 
Digital Inputs 
 
The digital input lines are CMOS/TTL compatible and can handle 
voltages from 0Vdc to +5Vdc. 
Digital Outputs 
 
The digital output lines have a maximum voltage of +5Vdc and 
are CMOS compatible. 
Ground 
 
This pin should be connected to the external digital devices 
ground. 
 
 
Table 2.1 - 485SDD16 I/O Port Pinout 
DB-25S 
Pin # 
 
Function 
DB-25S 
Pin # 
 
Function 
No connection 
14 
I/O #15 
No connection 
15 
I/O #14 
No connection 
16 
I/O #13 
No connection 
17 
I/O #12 
No connection 
18 
I/O #11 
No connection 
19 
I/O #10 
7 Ground 
20 No 
connection 
+12Vdc Input 
21 
I/O #9 
9 I/O 
#0 
22 I/O 
#8 
10 I/O 
#1 
23  I/O 
#7 
11 I/O 
#2 
24  I/O 
#6 
12 I/O 
#3 
25  I/O 
#5 
13 I/O 
#4 
 
 
6 485SDD16-1005 
Manual 
B&B Electronics  --  707 Dayton Road  --  Ottawa, IL  61350 
PH (815) 433-5100  --  FAX (815) 433-5104
 
 
Serial Port Connections 
 
In order to communicate to the 485SDD16 module it must be 
connected to an RS-422/RS-485 serial port.  The 485SDD16 will 
work on a 2-wire or 4-wire RS-485 multi-node network.  Refer to 
B&B Electronics’ free RS-422/485 Application Note for more 
information.  The unit automatically detects baud rates from 1200 to 
9600.  A data format of 8 data bits, 1 stop bit and no parity is used.  
Connections are made using terminal blocks.  Table 2.2 shows the 
terminal blocks and their functions. 
 
 
A typical 2-wire RS-485 connection is shown in Figure 2.3 and a 
typical RS-422 (or RS-485 4-wire) connection is shown in Figure 
2.4. Note that the 485SDD16 data line labels use “A” and “B” 
designators (per EIA RS-485 Specification). However, some RS-485 
equipment uses “+” and “-“ as designators. In almost all cases, the 
“A” line is the equivalent of the “-“ line and the “B” is the equivalent of 
the “+” line. With an RS-485/422 system there are other factors that 
require consideration, such as termination and turn-around delay. 
For more information refer to B&B Electronics’ free RS-422/485 
Application Note. 
Table 2.2 - RS-485 Terminal Block Connections 
 
TB 
Label  
 
 
Signal 
Signal 
Direction at 
485SDD16 
 
 
Notes 
FR 
GND 
Frame 
Ground 
Connection for frame ground. 
TD(A) Transmit 
Data (A) 
Output 
Connection is required. [Loop to 
RD(A) for 2-wire hookup] 
TD(B) Transmit 
Data (B) 
Output 
Connection is required. [Loop to 
RD(B) for 2-wire hookup] 
RD(A) Receive 
Data (A) 
Input 
Connection is required. [Loop to 
TD(A) for 2-wire hookup] 
RD(B) Receive 
Data (B) 
Input 
Connection is required. [Loop to 
TD(B) for 2-wire hookup] 
+12V +12 
Vdc 
Power  
Input Connection 
is 
required. 
GND 
Ground 
Connection for Signal GND and 
Power Supply GND.