ANCB/DN Specifications 
Protocol and Addressing 
Open Systems standard TCP/IP protocol and addressing 
(Transmission Control Protocol/Internet Protocol); Full Class A, B and 
C addresses and subnet masking supported 
Wiring Connections 
•  Two part connectors with screw-terminals provided for cable 
connection 
•  Fiber Optic Coupler for Fiber Optic Connections 
DataNET Option, Standard  
Cable 
•  Cable connection by Belden 9182 (single pair) or Belden 
SSD1743 (two pairs) or equivalent; two pairs of wires are 
required to support redundancy 
•  Two pairs of cable is required to support redundancy 
•  Shielded cable or unshielded cable in conduit is required for 
conformance to CE certified installation 
•  Two part connectors with screw-terminals provided for field 
connection 
DataNET Option, Fiber Optic 
Cable 
•  Fiber optics connection by 62.5 multi-mode cable corresponding 
to 10BaseFL Ethernet specification 
•  Two pairs of fibers are required to support redundancy 
•  Type ST mating connectors provided for field connection 
•  Approximately 3 mbps base transmission rate; uses dedicated 
transmission technique that does not require collision detection to 
achieve high data throughput efficiency 
•  Maximum Length 5000 feet ( 1.7km) 
Fiber Optic Coupler 
•  Two (Tx, Rx) ST-Style Connectors (Amp type 2.5mm Bayonet) 
 
 
Serial Port 
•  Standard RS-232 port for attachment of a laptop computer, for 
configuring IP Addresses and troubleshooting. 
 
Communication 
Comparisons 
The Table below compares key communication features between using 
Advance Data Hiway, Ethernet, or DataNET. 
Feature Advance 
Data 
Hiway 
Ethernet  DataNET 
Speed 
14.2 KB/Sec 
10 M baud 
2. 048 M baud 
Redundant Yes 
No 
Yes 
Number of Units in 
Maxum System 
248 1200 
1200 
 
2000592-001 
Installation 