Memory Areas
Appendix B
CS/CJ CPU Bus Unit Duplication Error Flag
Bit A40113 is turned ON when t
wo CS/CJ CPU Bus Units have been assigned the same unit number. The dupli-
cated unit number is indicated in A410.
CS/CJ CPU Bus Unit Error, Unit Number Flags
When an error occurs in a data exchange between the CPU Unit and an CS/CJ CPU Bus Unit, the CS/CJ CPU
Bus Unit Error Flag (A40207) is turned ON and the bit in A417 corresponding to the unit number of the Unit
where the error occurred is turned ON.
Bus Unit Error Flag (A40207) is turned ON and the bit in A417 corresponding to the unit number of the Unit
where the error occurred is turned ON.
CS/CJ CPU Bus Unit Restart Bits
Bits A50100 through A50115 can be turned ON to reset CS/CJ CPU Bus Units number #0 through #15,
respectively. The Restart Bits are turned OFF automatically when restarting is completed.
respectively. The Restart Bits are turned OFF automatically when restarting is completed.
CIO Area: CS/CJ CPU Bus Unit Area
The CS/CJ CPU Bus Unit Area (CIO Area) is allocated to CS/CJ CPU Bus Units according to the unit numbers
assigned to them, as shown below. Each Unit is allocated 25 words.
assigned to them, as shown below. Each Unit is allocated 25 words.
Error Information: CIO 1500 + 25
×
(Unit No.) (See page 304.)
Polling Node Address, Startup Node Address: CIO 1500 + 25
×
(Unit No.) + 1 (See page 304.)
Unit no.
Words
Unit no.
Words
0
1500 to 1524
8
1700 to 1724
1
1525 to 1549
9
1725 to 1749
2
1550 to 1574
10
1750 to 1774
3
1575 to 1599
11
1775 to 1799
4
1600 to 1624
12
1800 to 1824
5
1625 to 1649
13
1825 to 1849
6
1650 to 1674
14
1850 to 1874
7
1675 to 1699
15
1875 to 1899
1: Network parameter error (In PLC's EEPROM)
1: Data link table error (in PLC's EEPROM)
1: Data link table error (in PLC's EEPROM)
1: Routing table error (in PLC's EEPROM)
1: PLC system setting error
1: EEPROM error
1: EEPROM error
1: Duplicate node address setting error
1: Inconsistent network parameters
1: Communications controller send error
1: Communications controller hardware error
1: Error log exists
1: Communications controller hardware error
1: Error log exists
Polling node address
Startup node address
Each node address is displayed in 2-digit BCD.