348
Memory Areas
Appendix B
CS/CJ CPU Bus Unit Duplication Error Flag
Bit A40113 is turned ON when t
wo CS/CJ CPU Bus Units have been assigned the same unit number. The dupli-
cated unit number is indicated in A410.
CS/CJ CPU Bus Unit Error, Unit Number Flags
When an error occurs in a data exchange between the CPU Unit and an CS/CJ CPU Bus Unit, the CS/CJ CPU
Bus Unit Error Flag (A40207) is turned ON and the bit in A417 corresponding to the unit number of the Unit
where the error occurred is turned ON.
CS/CJ CPU Bus Unit Restart Bits
Bits A50100 through A50115 can be turned ON to reset CS/CJ CPU Bus Units number #0 through #15,
respectively. The Restart Bits are turned OFF automatically when restarting is completed.
CIO Area: CS/CJ CPU Bus Unit Area
The CS/CJ CPU Bus Unit Area (CIO Area) is allocated to CS/CJ CPU Bus Units according to the unit numbers
assigned to them, as shown below. Each Unit is allocated 25 words.
Error Information: CIO 1500 + 25 
×
 (Unit No.) (See page 304.)
Polling Node Address, Startup Node Address: CIO 1500 + 25 
×
 (Unit No.) + 1 (See page 304.)
Unit no.
Words
Unit no.
Words
0
1500 to 1524
8
1700 to 1724
1
1525 to 1549
9
1725 to 1749
2
1550 to 1574
10
1750 to 1774
3
1575 to 1599
11
1775 to 1799
4
1600 to 1624
12
1800 to 1824
5
1625 to 1649
13
1825 to 1849
6
1650 to 1674
14
1850 to 1874
7
1675 to 1699
15
1875 to 1899
1:  Network parameter error (In PLC's EEPROM) 
1:  Data link table error (in PLC's EEPROM)
1:  Routing table error (in PLC's EEPROM)
1:  PLC system setting error
1: EEPROM error
1:  Duplicate node address setting error
1:  Inconsistent network parameters
1:  Communications controller send error
1:  Communications controller hardware error
1: Error log exists
Polling node address
Startup node address
Each node address is displayed in 2-digit BCD.