Omron DR 170 14 Benutzerhandbuch

Seite von 67
Klinkmann Automation Omron Ethernet DAServer 
36 
 
 
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3                                                                 17014m13  
 
Item/point names, corresponding to CIO Area, may be without prefix. 
 
(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with 
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for long or 32-bit 
integer is from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999.  
Default value range for Integer Tag Type is unsigned integer. 
 
(**) Data cannot be written to addresses A000…A447 in the Auxiliary Area. 
 
(***) Current bank only (Memory Area code 98 in Hex). 
 
(****) Extended memory bank 0 to bank C (in Hex), up to 13 banks supported depending 
on CPU type. The prefix Ez can be one of the following: EA, EB, EC, ED, EE, EF, EG, 
EH, EI, EJ, EK, EL or EM. For read operations (both for Bit status and Words) and for 
Word write operations the Memory Area codes A0…AC (in Hex) are used. For Bit writing 
the Memory Area codes 20…2C (in Hex) are used. 
 
(*****) Read only. 
 
(******) Not supported on CJ1 controllers. 
 
The following examples show the correct format for item names for CS1 and CJ1 PLCs: 
 
CIO2:01     - 
CIO area (Bit status), word address 2, bit number 1. 
257   
CIO Area (Word contents), word address 257 
  H62.10 
Holding Area (Bit), word address 62, bit number 10 
  D21   
Data Memory Area with word address 21 
  EA12 
Extended Data Memory bank 0 word address 12 
  EC48.10 
Extended Data Memory bank 2 word address 48, bit number 10